MAINTENANCE
Troubleshooting
155
OrP
(15)
Phase lacked
Phase loss of power input
Action and Reset
Action level
DC bus is lower than
[PROT-06]
and DC bus ripple is higher than
[PROT-27]
Action time
Immediately
Related parameters
[PROT-28]
determines fault function.
[PROT-26]
is period between checks.
Reset method
Manually
Reset condition
Immediately reset when DC bus is higher than
[PROT-06]
Recorded
Yes
Possible Causes
Corrective Action
• Phase loss of input power
• Single phase power input to three-
phase model
• Power voltage changes
• Loose wiring terminal of input power
• The input cable of three-phase power
is cut off
• Input power voltage changes too
much
• Unbalanced three-phase of input
power
• Correctly install the wiring of the main circuit power.
• Choose the model whose power matches the voltage.
• If the main circuit power works normally, verify the main circuit. Cycle the power after checking the
power, if OrP error still exists, call Technical Support.
• Tighten the terminal screws according to the torque described in the user manual.
• Wire correctly. Replace the cut off cable.
• Verify the setting value for
IPO Check Time [PROT-26]
and
IPO Ripple [PROT-27]
.
• Check the power three-phase status.
Fault Display
Description
oSL
(63)
Over slip error
On the basis of the maximum slip limit set via
[MOTOR-19]
, the speed deviation is abnormal. When the motor drive out
-
puts at constant speed, F > H or F < H exceeds the level set via
[MOTOR-19]
, and it exceeds the time set via
[MOTOR-20]
,
oSL shows. oSL occurs in induction motors only.
Action and Reset
Action level
100% of
[MOTOR-19]
= the maximum limit of the slip frequency
Action time
[MOTOR-20]
Related parameters
Fault/Warning based on
[MOTOR-21]
Reset method
Auto
[MOTOR-21]
= 0 is a warning. When the motor drive outputs at constant speed, and F > H or F < H does not
exceed the level set via
[MOTOR-19]
anymore.
Manually
When
[MOTOR-21]
= 1 or 2, oSL is an error
Reset condition
Immediately
Recorded
[MOTOR-21]
= 1 or 2, oSL is “Fault” and will be recorded
Possible Causes
Corrective Action
• Any of the motor parameters may be
incorrect
• Overload
• Improper setup of feature
• Verify the motor parameters
• Decrease the load
• Verify the settings of
[MOTOR-18]
through
[MOTOR-21]
Fault Display
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...