MAINTENANCE
Troubleshooting
147
MVWV
(184)
M-VFD Wrong Ver
Wrong software version of drive operating Multi-VFD. Software version of follower (this drive) is different from the
master.
Action and Reset
Action level
[VFD-49]
different than master drive. To identify master drive, set
[SET-58]
to
23_Commu Role
. On screen, 0=No Role,
1=Master, and 2=Follower.
Action time
Immediately
Related parameters
[VFD-49]
Reset method
Reprogram drive
Reset condition
Immediately
Recorded
Yes
Possible Causes
Corrective Action
• Drive has different firmware VFD-49
than master.
• Reprogram drive with same firmware as master. To identify master drive, set
[SET-58]
to
23_Commu Role
.
On screen, 0=No Role, 1=Master, and 2=Follower.
• Replace drive with one that has matching firmware.
• Remove drive from network and operate independent.
Fault Display
Description
NOFL
(178)
No Flow(I)
Flow switch has detected no movement of fluid.
Action and Reset
Action level
Multi-function Input set to No Flow function is activated. Detection occurs after motor runs above min frequency for
duration of
Prime Time [IO-39]
and above
No-Flow Freq [IO-40]
.
No-Flow Mode [IO-38]
sets operation as
1_Trip
or
2_Sleep
where
additional condition of
No-Flow [IO-38]
has to be met to incur sleep mode.
Action time
Once detection occurs, MI has to be active for 5 secs.
Related parameters
[IO-38]
through
[IO-40]
;
[IO-20]
through
[IO-28]
;
[IO-46]
Reset method
Manually
Reset condition
MI becomes deactivated
Recorded
Yes
Possible Causes
Corrective Action
• No water (dry well)
• No-flow switch is Normally Closed
(closed when water is moving)
• Nuisance tripping
• Water flow is too low
• Pump has not finished filling pipe
with water
• Refill cistern or wait for well to fill with water
• Change
DI NO/NC [IO-46]
for designated input to NC.
• Review installation instructions with No-Flow Switch which include installing on long straight pipes
(no turns) and orientation (horizontal).
• Calibrate flow switch
• Increase Prime Time
Fault Display
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...