MAINTENANCE
Troubleshooting
186
PHL
(19)
Phase Loss Warn
Input phase loss warning
Action and Reset
Action condition
One of the phases outputs less than
[PROT-23]
Action time
[PROT-22]
Related parameters
[PROT-21]
= 0
Reset method
Automatically
Reset condition
After the drive stops
Recorded
N/A
Possible Causes
Corrective Action
• Phase loss of the input power
• Single phase power input on a three-
phase model
• The power voltage has changed
• Loose wiring terminal of input power
• Check if the input cable of 3-phase
power is broken
• The voltage of input power has changed
• Unbalance three-phase of the input
power
• Verify wiring of the main circuit.
• Use the model with voltage that matches the power.
• If the power of main circuit works well, check if the MC of the main circuit is broken. Cycle the power
after verifying the power is normal. If PHL still occurs, return to the factory for repair.
• Tighten the terminal screws with the torque listed in the user manual.
• Make sure the wiring is correct. Replace the broken part of the cable.
• Check setting for
IPO Check Time
[PROT-26]
and
IPO Ripple
[PROT-27]
.
• Check the status of three-phase power.
Warning Display
Description
PID
(11)
PID FBK Error
PID feedback loss (warning for analog feedback signal; works only when PID enables)
Action and Reset
Action condition
When the analog input is lower than 4 mA (only detects analog input of 4–20 mA)
Action time
N/A
Reset method
Automatically
Reset condition
Immediately reset
Recorded
Yes
Possible Causes
Corrective Action
• Loose or broken PID feedback wiring
• Feedback device malfunction
• Hardware error
• Tighten the terminals again. Replace with a new cable.
• Replace with a new feedback device.
• If the PID error still occurs after checking all the wiring, return to the factory for repair.
Warning Display
Description
PILA
(139)
Pipe Leak Alarm
Pipe leak detected in sleep mode where wake-up time is longer than
[ADV2-48]
,
[ADV2-49]
,
[ADV2-50]
, and
[ADV2-51]
.
Wake-up time is duration from pressure setpoint to wakeup level.
Action and Reset
Action condition
Pressure drops for a duration longer than wake-up time between PID setpoint (
[ADV2-52]
or and wakeup level)
Action time
Longer than
[ADV2-48]
,
[ADV2-49]
,
[ADV2-50]
, and
[ADV2-51]
Related parameters
[ADV2-46]
through
[ADV2-51]
Reset method
Fault/Warning is determined by
[ADV2-46]
Reset condition
Manually
Recorded
Yes
Possible Causes
Corrective Action
• Leak in pipe after pressure sensor
• System is low flow causing long delay to
reach wakeup level
• Pressurize pipe and then check for leaks
• Increase wake times
[ADV2-48]
to
[ADV2-51]
. Run system between different load demands and record
Last Wake Time [ADV2-47]
for each run. Set wake times larger than recorded value.
Warning Display
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...