SPECIFICATIONS
Common Specifications
235
SPECIFICATIONS
Common Specifications
Cooling Method
Forced air cooling by internal fans
Short Circuit Rating
The drive is suitable for use on a circuit capable of delivering not more than 100,000 symmetrical amperes (rms) when protected
by suitable Class J fuses.
Agency Approvals
UL and cUL listed, CE, marked.
CONTROL
Control Method
Pulse Width Modulation (PWM) with V/F and SVC (Sensorless Vector Control) for IM and PM motors.
Frequency Setting Resolution
Digital Reference: 0.01 Hz (Below 100 Hz), 0.1 Hz (Over 100 Hz)
Analog Reference: [Max. output frequency] x 0.03/60Hz (±11 bit)
Frequency Accuracy
Digital: ± 0.01 % of Max. Output Frequency. Analog: ± 0.1% of Max. Output Frequency.
V/F Control Curve
Linear curve, 1.5 power curve, square curve, 13 preset curves, and 4 point adjustable curve
Overload Capacity
Variable Torque: 120% of VFD rated current for 1 minute during every 5 minutes of operation.
Constant Torque: 120% of VFD rated current for 1 minute during every 5 minutes of operation and 160% for 3 seconds during
every 25 seconds of operation.
Starting Torque
Up to 150% or higher at 0.5 Hz (Torque Accuracy ± 5%).
Torque Limit (Stall level)
Variable Torque: Max. 130% torque current; Constant Torque: Max. 160% torque current
OPERATION
Operation Method
Keypad / Terminals / RS-485 BACnet or Modbus Communication / Optional Modbus TCP/IP & Ethernet IP
Frequency Setting
Two Analog Inputs 0- 10VDC/4-20mA and One AI 0-10VDC. Digital Input select, Keypad, or Communication
Inputs
Start Signal
Forward, Reverse, and Jog (some features can start and stop VFD based on analog signal)
Digital Inputs
8 programmable digital inputs can be set to any selection from long list of functions.
Multi-Step
Up to 17 Speeds can be set, including Jog by Programmable Digital Inputs.
Accel/Decel Time and Presets
0.00- 600.00/0.0- 6000.0 seconds. Three ACC/DEC preset values switched by digital inputs or one by frequency. Additional
adjustable Accel/Decel S-Curve pattern.
Emergency Stop
Ext. Trip and Shutdown immediately interrupt VFD output in any control method.
Jog
Jog Operation with adjustable Jog frequency
Fault Reset
Resets VFD via keypad, digital input, or communication. Some critical faults must be reset by recycling power.
Safety Inputs
SCM and STO terminals for safety circuit wiring.
Outputs
Three Multi-Function Relays
One relay with Form C: 250VAC 3A/30VDC, 3A (resistive) 1.2A (inductive) contact; Two relays with Form A: 250VAC 1.2A/
30VDC 3A (resistive) 1.2A (inductive). Each relay can be programmed to any selection from the functions list.
Two Analog Outputs
Selections: Output Frequency, Output Current, Output Voltage, Output kW, DC Link Voltage, Power Factor, AVI1, ACI, AVI2 AI
signal level, and constant output. Both outputs are 0-10VDC scalable from 10 to 200%.
General Operation Functions
DC Braking, Frequency Limit, Jump Frequencies, 2nd ACC/DEC, Auto Restart, Auto-Tuning, PID w/sleep, Flying Start, Speed
Search, DC Braking, Slip Compensation, Motor Pre-heat, Temperature Foldback, Damper Control, Fireman’s Override, Shut
-
down, Power-on Delay, Run Delay, Minimum Run Timer, PM Motor and FE MagForce Control and Auto-Tuning, trigger by Ana
-
log Level, Frequency High Limit by Analog Leve, Analog Repeater Output, Current Foldback, Scheduling, Single or three-phase
input, Auxiliary Timer, HOA Source selection, Keypad as OFF mode, 2/3-Wire Run Command, Hopping Carrier Frequency
Pump Operation Functions
Sleep Mode with Pressure Boost, Pipe Fill, PID, Overpressure, ULD (Underload), HLD (High Load), Broken Pipe, Backspin Timer,
MMC, Lubrication, Screen Clean, No-Flow Protection, Pump Prime Time, Clean Pump, Anti-jam, Multi-VFD, Jockey, Dual
Demand, Pipe Leak Detection, 2nd PID Operation, PT100/PTC Protection, Transducer Redundancy
PROTECTION
VFD Fault Trips
Over Voltage, Low Voltage, Over Current, Overload, Short Circuit, Ground Fault, VFD Overheat, Input Phase Loss, Output Phase
Open, CPU Communication Error, Signal Loss, Hardware Fault, Overpressure, Damper, No Flow, Trip by AI, various Multi-VFD,
Pipe Leak, Anti-Jam, etc.
VFD Alarm
Stall Prevention at ACC and DEC, Overload, Thermal Sensor Fault, Capacitors High Temperature, Signal Loss, Overpressure,
Underload, High Load, Pipe Leak, various Multi-VFD setup, App Disconnect, Limit by Level, etc.
Overcurrent
200/208/230/460VAC Variable Torque: At 185% of VFD rated current
200/208/230/460VAC Constant Torque: At 240% of VFD rated current
Current clamp: Variable Torque: 130- 135%, Constant Torque 170- 175%
575VAC models: At 225% VFD rated current
Current clamp: Variable Torque: 128- 141%, Constant Torque: 170- 175%
Overvoltage
230VAC models: At 410VDC DC bus voltage
460VAC models: At 820VDC DC bus voltage
575VAC models: At 1016VDC DC bus voltage
Fault History
Keypad provides 6 fault records. VFD logs 30 faults.
ENVIRONMENT
Operating Temperature
NEMA 1: -10 °C ~ 40 °C (14 °F ~ 104 °F), Open Type: -10 °C ~ 50 °C (14 °F ~ 122 °F)
Storage Temperature
-25 °C ~ 70 °C (-13 °F ~ 158 °F)
Ambient Humidity
Up to 95% RH (Non-Condensing)
Altitude
Normal up to 3,300 ft (1,000 m). At altitude up to 2,000 m, de-rate by 1% of rated current or lower 0.5 °C of temperature for
every 100 m above 1,000 m. Maximum altitude for Corner Grounded TN system is 2,000 m. For application over 2,000 m,
please contact Technical Support.
Vibration and Impact
1 mm peak to peak value from 2 Hz to 13.2Hz; 0.7G- 1.0G from 13.2 Hz to 55 Hz; 1.0G from 55 Hz to 512 Hz.
Comply with IEC 60068-2-6 and IEC/EN60068-2-27.
Environmental Conditions
Pollution degree 2. No Corrosive Gas, Combustible Gas, Oil Mist or Dust. IEC60721-3-3/ IEC60364-1/ IEC60664-1.
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...