PARAMETER REFERENCE TABLES
Parameter Descriptions > ADVANCE 2 Menu
230
ADV2-24 2072 Y AVI2 Mid %
-100 to 100%
Frequency output corresponding to
[ADV2-23]
input.
ADV2-25 2073 Y AVI2 High Value 0.00 to 10.0 V
Highest analog input value for AVI2 that corresponds to frequency output
of
[ADV2-26]
.
ADV2-26 2074 Y AVI2 High %
-100 to 100%
Frequency output corresponding to
[ADV2-25]
.
ADV2-27 2075 Y dEb Offset V
0.0 to 200.0 V
Decel Energy Backup Error (dEb) Offset Voltage that the DC Bus reduces
by to initiate dEb operation. Varies by VFD Rating.
ADV2-28 2076 Y dEb Mode Select 0_Disable
1_Auto Dec/Stop
2_AutoDec/Restart
Select Decel Energy Backup Error (dEb) operation when DC Bus voltage
drops by
[ADV2-27]
. This feature is used to detect power loss.
ADV2-30 2078 Y PID Mode Select 0_Serial P, I, D
1_Parallel P,I, D
0_Serial: VFD uses conventional PID control structure.
1_Parallel: Proportional, Integral, and Derivative gains are independent.
ADV2-31 2079 N PID Unit Format 0_1
1_0.1
2_0.01
Select precision of PID operation.
ADV2-32 2080 N PID Ref Source
0_Keypad
1_AVI1 Analog
2_ACI Analog
3_AVI2 Analog
4_RS-485
Select source of PID setpoint.
ADV2-36 2084 Y PID2 Output
0_No
1_Limit 1st PID
2_1st PID off
Used for Dual PID loop control. Default is No Limit.
0_ PID2 is disabled
1_Limit 1st PID, 2nd PID output frequency will become a 1st PID High Fre
-
quency Limit value. 2nd PID will vary its output based on the
[ADV2-38]
set-
point and Aux Ai signal values.
2_1st PID (in direct mode) maintains system pressure and 2nd PID (in
inverse mode) monitors tank or well level. Both PIDs are running simulta
-
neously but only one at a time provides speed reference to VFD.
ADV2-37 2085 Y PID2 Type
0_Direct
1_Inverse
Used for Dual PID loop control.
0_Direct: When feedback value is less than setpoint, then output
increases.
1_Inverse: When feedback value is less than setpoint, then output
decreases. This is the default setting.
ADV2-38 2086 Y PID2 Set Point
0 to
[ADV2-61]
PID2 target value for desired suction pressure.
ADV2-39 2087 Y PID2 P-Gain
0.0 to 100.0%
Proportional gain value for PID2 operation.
ADV2-40 2088 Y PID2 I-Time
0.00 to 100.00 sec
Integral gain value for PID2 operation.
ADV2-41 2089 Y PID2 Low Limit
[SET-22]
to
[ADV2-42]
Minimum frequency for PID2 output.
ADV2-42 2090 N PID2 High Limit
[ADV2-41]
to
[SET-23]
Maximum frequency for PID2 output.
ADV2-43 2091 Y PID2 Stp Delay
0.0 to 6000.0 min
Duration PID2 output is less than
[ADV2-41]
to fault causing "Low Level."
Only used if
[ADV2-36]
set to
2_1st PID off
.
ADV2-44 2092 Y PID2 Exit Lvl
0 to
[ADV2-61]
If feedback value is greater than
[ADV2-44]
for 10 seconds, then operation
switches from PID2 to PID1. Only used when
[ADV2-36]
set to
2_1st PID off
.
ADV2-45 2093 Y Dual Demand
0_Disabled
1_Enabled
With Dual Demand control, VFD will determine by wakeup time what
demand level is in the system.
ADV2-46 2094 Y Pipe Leak Sel
0_Disabled
1_P-Leak Alarm
2_P-Leak Trip
If wakeup time exceeds
H-H Wake Time [ADV2-48]
or
L-L Wake Time [ADV2-50]
,
VFD will activate Pipe Leak alarm or protection if activated.
ADV2-47 2095 Y Last Wake Time 0 to 6000 sec
Display duration from setpoint (High demand or Low Demand) to wakeup
level.
ADV2-48 2096 Y H-H Wake Time
0 to 6000 sec
(High to High Demand) is an adjustable setting for High to High Demand
wake up time, which should be determined during system startup. It is
recommended to set time in this parameter to 10-20% greater value than
[ADV2-47]
shows for proper Pipe Leak protection operation. Default = 4 sec
ADV2-49 2097 Y H-L Wake Time
0 to 6000 sec
(High to Low Demand) is an adjustable setting for High to Low Demand
wake up time, which should be determined during system startup. It is
recommended to set time in this parameter to 20-30% greater value than
[ADV2-47]
shows for proper Pipe Leak protection operation. Default = 10
sec.
CODE
Mod
Bu AR Display Name
Range
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...