SET-19 0019 N PID F/B Unit
0_PSI
1_inWC
2_Feet
3_F
4_CFM
5_GPM
6_%
7_Cust
8_inHg
9_m
10_mBar
11_Bar
12_kPa
13_C
14_LPM
15_CMH
Measurement unit selection for feedback signal.
SET-20 0020 N PID F/B Max
0.0 to 32767
PID feedback transducer maximum range
SET-21
0021 Y PID Set-point
0.0 to
[SET-20]
(
[SET-19]
Unit) Set the desired value for PID (pressure, temperature, GPM, etc.).
SET-22 0022 Y PID Lo Hz Limit
[SET-13]
to
[SET-23]
(Hz)
Low frequency limit in PID mode. PID Low Frequency is limited by
Low Frequency [SET-13]
and
PID High Frequency [SET-23]
.
SET-23 0023 N PID Hi Hz Limit
[SET-22]
to
[SET-14]
(Hz)
High frequency limit in PID mode. PID High Frequency is limited by
High Fre
-
quency [SET-14]
and
PID Low Frequency [SET-22]
.
SET-24 0024 Y PID P-Gain
0 to 100%
Proportional-Gain determines PID control sensitivity. Greater values pro
-
vide more sensitivity. However, if set too high, the system may create an
output frequency oscillation and instability. Used along with
PID I-TIme [SET-25]
to smooth and balance system response.
SET-25 0025 Y PID I Time
0.0 to 100 sec
Integral-Time determines PID response time. Lower values increase system
response to the feedback signal, which reduces overshoot, but may cause
system oscillation if set too low. Greater values provide slower response,
which may cause overshoot of the setpoint and oscillation of output fre
-
quency.
SET-26 0026 Y Sleep Mode
0_Disabled
1_Sleep Only
Boost
Sleep Mode selection for pressure controlled systems, such as pumping
applications. Boost increases the process control value (pressure)
before going to sleep.
SET-27 0027 Y Sleep Chk Time
5 to 120 sec
Time delay (sleep check cycle time) before each Sleep Check process.
SET-28 0028 Y Sleep Delay
0 to 3000 sec
Delay before VFD triggers Sleep Mode state when all other conditions are
met.
SET-29 0029 Y S-Boost Value
0 to 10%
Sleep Boost Value: Value added to original setpoint to provide a pressure
boost before entering sleep.
SET-30 0030 Y S-Boost Timer
5 to 120 sec
Sleep Boost Timer: Limits duration of sleep boost operation if Sleep Boost
set-point is not reached.
SET-31
0031 Y Wake-Up Level
0.0 to
[SET-21]
(
[SET-19]
Unit)
Sets a wakeup level for VFD to exit Sleep mode and start running.
SET-32 0032 Y S-Bump Timer
5 to 120 sec
Sleep Bump Timer: Sets a duration time for pressure bump to increase sys
-
tem pressure.
SET-33 0033 Y Pipe Fill Timer
0.0 to 60 min
Pipe Fill mode exit timer to switch to PID mode. If set to 0.0 min, pipe fill is
disabled.
SET-34 0034 Y P-Fill Exit Lvl
0.0 to
[SET-21]
(
[SET-19]
Unit)
If feedback reaches
[SET-34]
value, VFD will switch from pipe fill mode to PID
control mode.
SET-35 0035 Y Pipe Fill Freq
[SET-22]
to
[SET-23]
(Hz)
VFD will vary the output frequency from
[ADV2-68]
to
[SET-35]
trying to main
-
tain 60% of
[SET-34]
value.
SET-36 0036 Y Broken Pipe Lvl
0.0 to
[SET-21]
(PSI)
If VFD runs above
[SET-37]
frequency for
[SET-38]
delay with system pressure
below
[SET-36]
, it will trip on Broken Pipe fault. If
[SET-36]
is set to 0, this pro
-
tection will be disabled.
SET-37 0037 Y Broken Pipe Frq
[SET-22]
to
[SET-23]
(Hz)
If VFD is running above this speed with pressure below
[SET-36]
, Broken Pipe
Delay timer starts.
SET-38 0038 Y Broken Pipe Dly 0 to 6000 sec
If Broken Pipe Delay timer runs longer than this setting, VFD trips on Broken
Pipe fault.
SET-39 0039 Y OverPress Set
0_Disabled
1_OP Trip
2_OP Auto Reset
Overpressure protection settings
OP Trip: When tripped on overpressure, VFD will require a reset.
OP Auto Reset: occurs when pressure drops below
Wake-up Level [SET-31]
.
CODE Mod
Bus AR Display Name
Range
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...