PARAMETER REFERENCE TABLES
Parameter Descriptions > I/O Menu
211
IO-21
0533 Y MI1 Define
0_No Function
1_Speed-L
2_Speed-M
3_Speed-H
4_Speed-X
5_Fault Reset
6_Jog Speed
7_Hold Speed
8_XCEL-L
9_XCEL-M
10_Ext. Trip
11_3-Wire Stop
12_AVI1 Analog Spd
13_ACI Analog Spd
14_AVI2 Analog Spd
16_Up
17_Down
18_PID Disable
19_CLR CNT
20_Input CNT (MI6)
21_FWD Jog
22_REV Jog
25_E-Stop
26_HOA-HAND
27_HOA-AUTO
28_Drive Enabled
29_PLC mode bit 0
30_PLC mode bit 1
32_FO with RUN Cmd
33_FO w/o RUN Cmd
34_Damper Limit Sw
35_Shutdown N-Latch
36_Shutdown Latched
37_Flow Switch
38_FWD
39_REV
40_Aux Motor-1 OFF
41_Aux Motor-2 OFF
42_Aux Motor-3 OFF
43_Aux Motor-4 OFF
44_Aux Motor-5 OFF
45_Aux Motor-6 OFF
46_Aux Motor-7 OFF
47_All Aux Mtr Off
48_Set-Point-A
49_Set-Point-B
MI1 Default = Speed-L
1_Multi-step speed command 1
2_Multi-step speed command 2
3_Multi-step speed command 3
4_Multi-step speed command 4
5_Use to reset fault after cause is corrected
6_Changes speed in jog mode to value set in
[VFD-55]
7_When active, VFD will hold current speed
8_ACC/DEC time will be changed to
[VFD-19]
and
[VFD-20]
9_ACC/DEC time will be changed to
[VFD-21]
and
[VFD-22]
10_Trips VFD by external protective device and requires reset
11_Stop input for 3-Wire control, MI1 by default
12_In non-PID mode, changes speed reference to AVI1
13_In non-PID mode, changes speed reference to ACI
14_In non-PID mode, changes speed reference to AVI2
16_Increases speed reference when
[SET-07]
is set to (1)
17_Decreases speed reference when
[SET-07]
is set to (1)
18_Disables PID and switches speed reference to keypad
19_Clears pulse counter accumulated value (MI6 only)
20_Pulse counter input (MI6 only)
21_Jog Command Forward
22_Jog Command Reverse
25_VFD stops by Emergency Stop device (requires reset)
26_External HOA Hand position contact
27_External HOA Auto position contact
28_Enables and disables the drive (not a run command)
29_ PLC Function Disable 29 and 30=(0) or Run 29= (1)
30_ PLC Function Disable 29 and 30=(0) or Stop 30= (1)
32_VFD will start in FO Mode by FO DI and Run Command
33_VFD will start in FO Mode by FO DI (No Run Command)
34_When damper is closed, Damper LSW DI is activated
35_Activates Shutdown. When inactive, VFD operates normally
36_Activates Shutdown. Requires reset to operate normally
37_Detects water or air flow by Flow Switch
38_Provides an option to replace the dedicated FWD input
39_Provides an option to replace the dedicated REV input
40_Aux Motor-1 in MMC mode is off sequence
41_Aux Motor-2 in MMC mode is off sequence
42_Aux Motor-3 in MMC mode is off sequence
43_Aux Motor-4 in MMC mode is off sequence
44_Aux Motor-5 in MMC mode is off sequence
45_Aux Motor-6 in MMC mode is off sequence
46_Aux Motor-7 in MMC mode is off sequence
47_All Aux Motors in MMC mode are off sequence
48_Preset Set-Point-A for PID control
49_Preset Set-Point-B for PID. (If 48 and 49 ON=S-point-AB)
IO-22
0534 Y MI2 Define
See
[IO-21]
MI2 Default = Preset Speed-M
IO-23
0535 Y MI3 Define
See
[IO-21]
MI3 Default = Preset Speed-H
IO-24
0536 Y MI4 Define
See
[IO-21]
MI4 Default = Fault Reset
IO-25
0537 Y MI5 Define
See
[IO-21]
MI5 Default = Emergency Stop
IO-26
0538 Y MI6 Define
See
[IO-21]
MI6 Default = XCEL-L (ACC-2/ DEC-2 Time)
IO-27
0539 Y MI7 Define
See
[IO-21]
No Function
IO-28
0540 Y MI8 Define
See
[IO-21]
No Function
IO-29
0541 N FO Enable
0_Disable
1_FWD Operation
2_REV Operation
Enables Fireman’s Override mode in either forward or reverse.
IO-30
0542 Y FO Frequency
[SET-13]
to
[SET-14]
(Hz)
Preset frequency for non-PID Fireman’s Override mode.
IO-31
0543 Y FO Fault Retry
0 to 10
Number of auto-retries during fault in Fireman’s Override mode
IO-32
0544 Y FO Retry Delay
0 to 6000 sec
Delay of auto-retries during fault in Fireman’s Override mode
CODE Mod
Bus AR Display Name
Range
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...