PARAMETER REFERENCE TABLES
Parameter Descriptions > I/O Menu
213
IO-47
0559 Y Relay RA1
0_No Function
1_Run
2_FDT-1
3_FDT-2
4_FDT-3
5_FDT-4
6_FDT-5
7_Drive Ready
8_Fault
9_VFD Overheat
10_DC Brake
11_PID F/B Loss
12_Counter Done
13_Pre-Count Done
14_Alarm
15_FWD CMD
16_REV CMD
17_Analog Trigger
19_Overcurrent 2
20_High Load
21_Under Load
22_Fireman O-ride
23_Bypass
24_Motor-1 Out
25_Motor-2 Out
26_Motor-3 Out
27_Motor-4 Out
28_Motor-5 Out
29_Motor-6 Out
30_Motor-7 Out
31_Pipe Leak
32_Preheat Output
33_Steady
34_Pre-PID
35_Sleep
36_Speed Search
37_Pipe Broken
38_Damper Output
39_Aux Timer Out
40_Overpressure
41_Lube/S Clean
42_ACI Loss
43_AVI1 Loss
44_Hand Mode
45_Auto Mode
47_MMC Out
48_Jockey Pump
49_At High Current
50_At Low Current
RA1 Default = Fault
1_During Run Mode
2_When frequency reference value is achieved
3_On above
[IO-52]
freq and Off below
[IO-52]
-
[IO-53]
freq
4_On above
[IO-54]
freq and Off below
[IO-54]
+
[IO-55]
freq
5_On up to FDT-4/5 freq
6_On above FDT-4/5 freq
7_When drive is powered and ready (no faults)
8_When drive has tripped on any fault
9_When VFD temperature reaches trip level
10_When DC injection brake is activated
11_When PID feedback source signal value is abnormal
12_When pulse counter achieves the counter set-value
13_When pulse counter achieves pre-count value
14_When alarm is triggered by any alarm condition
15_When VFD operates in Forward direction
16_When VFD operates in Reverse direction
17_When analog signal reaches a trigger level
19_When VFD trips on Overcurrent 2
20_HLD triggered
21_ULD triggered
22_When Fireman’s Override mode is activated
23_When drive switches from Soft-Start mode to Bypass
24_When Motor-1 is enabled in MMC control
25_When Motor-2 is enabled in MMC control
26_When Motor-3 is enabled in MMC control
27_When Motor-4 is enabled in MMC control
28_When Motor-5 is enabled in MMC control
29_When Motor-6 is enabled in MMC control
30_When Motor-7 is enabled in MMC control
31_Pipe Leak protection is triggered
32_VFD provides Motor Preheat output
33_VFD provides steady freq output
34_VFD is in Pipe Fill mode
35_VFD is in Sleep mode
36_VFD is in Speed Search mode
37_Pipe Broken protection is triggered
38_When Damper motor output is activated
39_Auxiliary timer output
40_Overpressure is triggered
41_When Lube or Screen Clean solenoid output is activated
42_When ACI analog input signal loss is detected
43_When AVI1 analog input signal loss is detected
44_When VFD control is in Hand mode
45_When VFD control is in Auto mode
47_Aux motor start output in MMC control
48_Jockey pump start output
49_When current reaches High Current trigger level
50_When current is below Low Current trigger level
IO-48
0560 Y Relay RA2
See
[IO-47]
RA2 Default = Run
IO-49
0561 Y Relay RA3
See
[IO-47]
RA3 Default = FDT-4
IO-50
0562 Y CNT Attained 0
0 to 65500
Active increment counter triggered by MI6 when
[IO-26]
is set to
20_Input CNT
.
After completion of counting, the relay output becomes active if
[IO-47]
,
[IO-48]
, or
[IO-49]
is set to
13_PreCount Done
. The relay becomes active for 1
msec. The counter then returns to 0.
When the display shows c5555, the drive has counted 5,555 times. If display
shows c5555*, it means that real counter value is between 55,550 to 55,559.
IO-51
0563 Y CNT Attained 1
0 to 65500
Increment counter triggered by MI6 when
[IO-26]
is set to
20_Input CNT
. After
completion of counting, the relay output becomes active if
[IO-47]
,
[IO-48]
, or
[IO-49]
is set to
12_Count Done
. The relay stays active for same number of
counts then becomes inactive. The cycle then repeats.
IO-52
0564 Y FDT-2 Frequency 0.0 to 600 Hz
Relay is activated when during ACC frequency is above
[IO-52]
. Relay will be
deactivated when frequency is below (
[IO-52]
-
[IO-53]
).
CODE Mod
Bus AR Display Name
Range
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...