MAINTENANCE
Troubleshooting
140
EF
(49)
External Fault
Drive stops based on signal from an external device.
Action and Reset
Action level
When a multi-function input terminal (MI1 to MI8) is set to
10_Ext Trip Terminal
and the contact is closed, the AC motor
drive stops output based on
[IO-35]
setting.
Action time
Immediately
Related parameters
Ext Trip Mode [IO-35]
;
[IO-21]
to
[IO-28]
Reset method
Manually
Reset condition
After external error has been corrected.
Recorded
Yes
Possible Causes
Corrective Action
• Multi-function input terminal that is
set to external fault has been
activated.
• Deactivate input terminal with function set to external fault
• Check Normally Open / Normally Closed settings for
DI NO/NC [IO-46]
Fault Display
Description
EF1
(50)
Emergency stop
Drive has been stopped through an external switch
Action and Reset
Action level
When a multi-function input terminal (MI1 to MI8) is set to emergency stop and the contact is closed, the AC motor
drive stops output and the motor coasts to stop.
Action time
Immediately
Related parameters
MI1 [IO-21]
to
MI8 Define [IO-28]
Reset method
Manually
Reset condition
After external error has been corrected.
Recorded
Yes
Possible Causes
Corrective Action
• Multi-function input terminal that is
set to emergency stop has been
activated.
• Deactivate input terminal with function set to emergency stop
• Check Normally Open / Normally Closed settings
DI NO/NC [IO-46]
Fault Display
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...