ELECTRICAL INSTALLATION
Control Circuit Connections
46
NPN and PNP Digital Inputs Configuration
Cerus X-Series drive control can be configured to Sink (NPN) or Source (PNP) modes by providing proper
wiring and installing/removing jumper on ter24, COM and DCM.
The picture above shows four possible digital inputs configurations:
1.
Sink (NPN) mode with internal 24VDC power source (Default).
Install jumper b24 and COM
terminals. Connect dry contact or NPN transistor output from external control device to desired digital
input and DCM terminals. When contact is closed or transistor is in conducting state, digital input will
be activated by internal power supply.
2.
Source (PNP) mode with internal 24VDC power source.
Install jumper between DCM and COM termi
-
nals. Connect dry contact or PNP transistor output from external control device to desired digital input
and +24 terminals. When contact is closed or transistor is in conducting state, digital input will be acti
-
vated by internal power supply.
3.
Sink (NPN) mode with external 24VDC power source.
Remove any jumpers b24 and COM or
DCM and CM terminals. Connect positive terminal of external power supply to COM terminal. Connect
dry contact or NPN transistor output from external control device to desired digital input and negative
terminal of external power supply. When contact is closed or transistor is in conducting state, digital
input will be activated by external power supply.
4.
Source (PNP) mode with external 24VDC power source.
Remove any jumpers b24 and COM
or DCM and CM terminals. Connect negative terminal of external power supply to COM terminal. Con
-
nect dry contact or PNP transistor output from external control device to desired digital input and pos
-
itive terminal of external power supply. When contact is closed or transistor is in conducting state,
digital input will be activated by external power supply.
+
+
++
+
1
2
3
4
MI1
FWD
MI8
NPN
+24 V
COM
DCM
Internal circuit
MI1
FWD
Internal circuit
DCM
+24 V
MI8
COM
External Power +24 V
Internal circuit
DCM
+24 V
NPN
MI1
FWD
MI8
COM
External Power +24 V
MI1
FWD
MI8
DCM
COM
+24 V
Internal circuit
PNP
PNP
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...