MAINTENANCE
Troubleshooting
161
SfLk
(112)
PMLess ShaftLock
The drive has RUN command with output frequency, but the permanent magnetic motor does not turn.
Action and Reset
Action level
Software detection
Action time
3 sec.
Reset method
Manually
Reset condition
Immediately
Recorded
Yes
Possible Causes
Corrective Action
• Improper setting of the speed
observer bandwidth
• Motor shaft lock
• Motor error (e.g. demagnetization)
• Increase the setting value
• Remove causes of the motor shaft lock
• Replace the motor with a new one
Fault Display
Description
SHDN
(179)
Shutdown
Shutdown detected on Multi-function input
Action and Reset
Action level
Multi-function Input set to Shutdown N-Latch or Shutdown Latched
Action time
Immediately
Related parameters
[IO-20]
through
[IO-28]
;
[IO-46]
Reset method
Auto
Shutdown N-Latch (not latch)
Manually
Shutdown Latch
Reset condition
Deactivate MI corresponding to Shutdown Latch and Shutdown N-Latch
Recorded
Yes
Possible Causes
Corrective Action
• External device activating shutdown
• Nuisance tripping
• External shutdown switch is Normally
Closed circuit (no shutdown with
switch closed)
• Reset external device causing shutdown
• Adjust
DI filter [IO-20]
• Set MI to NC with
DI NO/NC [IO-46]
Fault Display
Description
STL1
(72) STO Loss 1
STL2
(77) STO Loss 2
STL3
(78) STO Loss 3
Safe Torque Off Loss 1: STO1–SCM1 internal loop detection error
Safe Torque Off Loss 2: STO2–SCM2 internal loop detection error
Safe Torque Off Loss 3: STO1–SCM1 and STO2–SCM2 internal loop detection error
Action and Reset
Action level
Hardware detection
Action time
Immediately
Reset method
Cycle the power.
Reset condition
N/A
Recorded
Yes
Possible Causes
Corrective Action
• Short circuit lines are not connected
• Hardware failure
• Bad connection of the IO card
• The IO card does not match the
version of the control board
• Connect the short circuit line. After you make sure all the wiring is correct, if fault still exists after
cycling the power, please return to the factory for repair.
• Check if the PIN of IO card is broken.
• Check if the IO card connects to the control board correctly, and if the screws are tightened well.
• For incorrect version, contact Technical Support.
Fault Display
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...