DRIVE CONFIGURATION
Default Settings Table - ADV Menu
55
ADV-22 MMC Decel Time
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
ADV-23 Lag Stop Freq
35 Hz
35 Hz
35 Hz
35 Hz
35 Hz
35 Hz
35 Hz
35 Hz
70 Hz
50 Hz
ADV-24 Lag Stop Delay
4 Sec
4 Sec
4 Sec
4 Sec
4 Sec
4 Sec
4 Sec
4 Sec
4 Sec
4 Sec
ADV-25 Lag Stop Level
0.3%
0.3%
0.3%
0.3%
0.3%
0.3%
0.3%
0.3%
0.3%
0.3%
ADV-26 Lead Freq Bump
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
ADV-27 MMC Accel Time
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
ADV-28 Power-On Delay
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
ADV-29 Run Delay Timer
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
ADV-30 Backspin Timer
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
ADV-31
Aux Timer Type
On-Delay
On-Delay
On-Delay
On-Delay
On-Delay
On-Delay
On-Delay
On-Delay
On-Delay
On-Delay
ADV-32 Aux Timer Time
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
ADV-33 Aux Timer Input
FWD DI
FWD DI
FWD DI
FWD DI
FWD DI
FWD DI
FWD DI
FWD DI
FWD DI
FWD DI
ADV-34 Min Run Timer
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
ADV-35 Multi-VFD Set
Single VFD Single VFD Single VFD Single VFD Single VFD Single VFD Single VFD Single VFD Single VFD Single VFD
ADV-36 Standby Pumps
0
0
0
0
0
0
0
0
0
0
ADV-37 Multi-VFD ID
VFD-1
VFD-1
VFD-1
VFD-1
VFD-1
VFD-1
VFD-1
VFD-1
VFD-1
VFD-1
ADV-38 VLag Start Freq
59.5 Hz
59.5 Hz
59.5 Hz
59.5 Hz
59.5 Hz
59.5 Hz
59.5 Hz
59.5 Hz
114 Hz
114 Hz
ADV-39 VLag Start Delay
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
ADV-40 VLag Stop Freq
35 Hz
35 Hz
35 Hz
35 Hz
35 Hz
35 Hz
35 Hz
35 Hz
70 Hz
50 Hz
ADV-41 VLag Stop Delay
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
ADV-42 VLead/Lag ID
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only
Read Only
Read Only
ADV-43 VLag Spd Source
PID
PID
PID
PID
PID
PID
PID
PID
PID
PID
ADV-44 VLag Set Freq
55 Hz
55 Hz
55 Hz
55 Hz
55 Hz
55 Hz
55 Hz
55 Hz
110 Hz
110 Hz
ADV-45 Alternation
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
ADV-46 Alternate TMR
24 Hour
24 Hour
24 Hour
24 Hour
24 Hour
24 Hour
24 Hour
24 Hour
24 Hour
24 Hour
ADV-47 Set VFD Ready
Ready
Ready
Ready
Ready
Ready
Ready
Ready
Ready
Ready
Ready
ADV-48 Jockey Mode
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
ADV-49 J-Start Press
0.5 inWC
0.5 inWC
0.5 inWC
75 °F
54 PSI
54 PSI
54 inWC
54 PSI
54 PSI
0.5 inWC
ADV-50 J-Start Freq
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
100 Hz
100 Hz
ADV-51 Main Stop Freq
40 Hz
40 Hz
40 Hz
40 Hz
40 Hz
40 Hz
40 Hz
40 Hz
80 Hz
80 Hz
ADV-52 J-Start Delay
20 Sec
20 Sec
20 Sec
20 Sec
20 Sec
20 Sec
20 Sec
20 Sec
20 Sec
20 Sec
ADV-53 Main Stop Delay
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
5 Sec
ADV-55 AVR Select
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
ADV-56 Prog-1 Setting
None
None
None
None
None
None
None
None
None
None
ADV-57 Prog-1 On Time
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
ADV-58 Prog-1 Off Time
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
ADV-59 Prog-1 Week Day
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
ADV-60 Prog-2 Setting
None
None
None
None
None
None
None
None
None
None
ADV-61 Prog-2 On Time
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
ADV-62 Prog-2 Off Time
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
ADV-63 Prog-2 Week
Day
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
ADV-64 Prog-3 Setting
None
None
None
None
None
None
None
None
None
None
ADV-65 Prog-3 On Time
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
ADV-66 Prog-3 Off Time
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
ADV-67 Prog-3 Week
Day
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
ADV-68 Prog-4 Setting
None
None
None
None
None
None
None
None
None
None
ADV-69 Prog-4 On Time
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
ADV-70 Prog-4 Off Time
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
00:01
ADV-71
Prog-4 Week
Day
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
ADV-74 Set-Point-A
0.5 inWC
0.5 inWC
0.5 inWC
76 °F
60 PSI
60 PSI
60 inWC
60 PSI
60 PSI
0.5 inWC
ADV-75 Set-Point-B
0.5 inWC
0.5 inWC
0.5 inWC
76 °F
60 PSI
60 PSI
60 inWC
60 PSI
60 PSI
0.5 inWC
ADV-76 Set-Point-AB
0.5 inWC
0.5 inWC
0.5 inWC
76 °F
60 PSI
60 PSI
60 inWC
60 PSI
60 PSI
0.5 inWC
CODE
Display
Basic
Supply Fan
Exhaust
Fan
Cooling
Tower
Centrifugal
Pump
Submersible
Pump
Vacuum
Pump
Constant
Torque
FE MagForce PM Motor
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...