MAINTENANCE
Troubleshooting
137
cd3
(35)
Ics sensor Err
W-phase current detection error when power is ON
Action and Reset
Action level
Hardware detection
Action time
Immediately
Reset method
Cycle the power
Recorded
Yes
Possible Causes
Corrective Action
• Hardware failure
• If error still exists after power cycle, please call Technical Support.
Fault Display
Description
CE2
(55) PC Err address
CE1
(54) PC Err command
CE3
(56) PC Err data
CE4
(57) PC slave fault
Data address is illegal
Communication command is illegal
Data value is illegal
Data is written to read-only address
Action and Reset
Action level
When the function code is not 03, 06, 10, or 63.
Action time
Immediately
Related parameters
[Comm-02]
Reset method
Manually
Reset condition
Immediately
Recorded
No
Possible Causes
Corrective Action
• Incorrect communication command
from the master unit
• Malfunction caused by interference
• Different communication setting from
the master unit
• Disconnection or bad connection of
the cable
• Check if the communication command is correct.
• Verify the wiring and grounding of the communication circuit. It is recommended to separate the
communication circuit from the main circuit, or wire in 90 degree for effective anti-interference
performance.
• Check if the setting for
[Comm-02]
is the same as the setting for the master unit.
• Check the cable and replace it if necessary.
Fault Display
Description
CE10
(58)
PC time out
Modbus transmission time-out occurs
Action and Reset
Action level
When the communication time exceeds the detection time for
[Comm-03]
time-out
Action time
[Comm-03]
Related parameters
[Comm-02]
Reset method
Manually
Reset condition
Immediately
Recorded
Yes
Possible Causes
Corrective Action
• The upper unit does not transmit the
communication command within
[Comm-03]
setting time.
• Malfunction caused by interference
• Different communication setting from
the master unit
• Disconnection or bad connection of
the cable
• Check if the master unit transmits the communication command within
[Comm-03]
• Verify the wiring and grounding of the communication circuit. It is recommended to separate the
communication circuit from the main circuit, or wire in 90 degree for effective anti-interference
performance.
• Check if the setting for
[Comm-02]
is the same as the setting for the master unit.
• Check the cable and replace it if necessary.
Fault Display
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...