PARAMETER REFERENCE TABLES
Parameter Descriptions > COMM Menu
223
Parameter Descriptions > COMM Menu
AR = Adjustable while running.
PROT-43 1067 Y Spd Search Gain 1 to 200%
Speed search gain: Voltage gain percentage for speed search operation.
Reduce value if overload or over-current fault occurs.
PROT-44 1068 Y IPF Restart Dly
0.0 to 5.0 sec
Delay for restart after an Instantaneous Power Failure. Set value high
enough to allow residual regeneration voltage to disappear.
PROT-45 1069 Y Fan Control
0_At Power-Up
1_Delayed Stop
2_During Run
3_By Temperature
4_Disabled
Determines operation of fan. It is not recommended to set to
4_Disabled
since this will reduce performance of drive.
3_Starts fan at 60 °C
PROT-46 1070 Y Last Flt Freq
0.00 to 599.00 Hz
Output frequency at last fault (Read Only)
PROT-47 1071 Y Last Flt IGBTT
-3277 to 3276.7 °C
IGBT temperature at last fault (Read Only)
PROT-48 1072 Y Last Flt Cap T
-3277 to 3276.7 °C
Capacitance temperature at last fault (Read Only)
PROT-49 1073 Y Last Flt MFI
0000h to FFFFh
Status of Multi-function input terminals at last fault (Read Only)
PROT-50 1074 Y Last Flt MFO
0000h to FFFFh
Status of Multi-function output terminals at last fault (Read Only)
PROT-51 1075 Y Fault-1 Record
0 to 65535
First register of fault listing. (Read Only)
PROT-52 1076 Y Fault-2 Record
0 to 65535
Second register of fault listing. (Read Only)
PROT-53 1077 Y Fault-3 Record
0 to 65535
Third register of fault listing. (Read Only)
PROT-54 1078 Y Fault-4 Record
0 to 65535
Fourth register of fault listing. (Read Only)
PROT-55 1079 Y Fault-5 Record
0 to 65535
Fifth register of fault listing. (Read Only)
PROT-56 1080 Y Fault-6 Record
0 to 65535
Sixth register of fault listing. (Read Only)
PROT-57 1081 Y ULD Torque Min 5% to
[SET-42]
Sets minimum torque level % at 0Hz when using Underload Torque.
PROT-58 1082 Y HLD Torque Min
[PROT-57]
to
[SET-48]
Sets minimum torque level % at 0Hz when using High load Torque.
CODE Mod
Bus AR Display Name
Range
Description
CODE
Mod
Bus AR Display Name
Range
Description
Comm-00 1280 Y COM1 Address
1 to 254
RS485 address of VFD.
Comm-01 1281 Y COM1 Speed
4.8 to 115.2 Kbps
RS485 baud rate. All devices on RS485 communication must have the
same baud rate.
Comm-02 1282 Y COM1 Loss
0_Alarm and Run
1_Trip Decel Stop
2_Trip Coast Stop
3_Disabled
Select operation when communication is lost.
Comm-03 1283 Y COM1 Loss Delay 0.0 to 100.0 sec
Duration of communication loss before initiating operation.
Comm-04 1284 Y COM1 Protocol
1_7, N, 2 for ASCII
2_7, E, 1 for ASCII
3_7, O, 1 for ASCII
4_7, E, 2 for ASCII
5_7, O, 2 for ASCII
6_8, N, 1 for ASCII
7_8, N, 2 for ASCII
8_8, E, 1 for ASCII
9_8, O, 1 for ASCII
10_8, E, 2 for ASCII
11_8, O, 2 for ASCII
12_8, N, 1 for RTU
13_8, N, 2 for RTU
14_8, E, 1 for RTU
15_8, O, 1 for RTU
16_8, E, 2 for RTU
17_8, O, 2 for RTU
RS485 Protocol: Data Bits - Parity - Stop Bits - Message Format
Comm-05 1285 Y Response Delay 0.0 to 200.0 ms
Duration VFD waits before responding to received communication.
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...