MAINTENANCE
Troubleshooting
160
RoPd
(89)
Rotor Pos. Error
Rotor position detection error protection
Action and Reset
Action level
Software detection
Action time
Immediately
Reset method
Manually
Reset condition
Immediately
Recorded
Yes
Possible Causes
Corrective Action
• Motor cable is abnormal or broken
• Motor coil error
• Hardware fialure
• Drive’s current feedback line error
• Check cable and replace as needed
• Replace motor
• IGBT broken. Call Technical Support.
• Cycle the power. If RoPd still occurs during operation, call Technical Support.
Fault Display
Description
ryF
(64)
MC Fault
Electric valve switch error when executing Soft Start
Action and Reset
Action level
Hardware detection (Frame D and above)
Action time
Immediately
Reset method
Manually
Reset condition
Reset when the electric value switch is correctly closed
Recorded
Yes
Possible Causes
Corrective Action
• The input power is abnormal
• Malfunction caused by interference
• Hardware failure
• Check if the power is shut down during the drive operation
• Check if the three-phase input power is normal
• Verify the wiring/grounding of the main circuit to prevent interference
• Cycle the power after checking the power. If ryF error still exists, call Technical support
Fault Display
Description
S1
(73)
S1-emergy stop
Emergency stop for external safety
Action and Reset
Action level
Hardware detection
Action time
Immediately
Reset method
Manually
Reset condition
Reset only after S1 error is cleared
Recorded
Yes
Possible Causes
Corrective Action
• The switch action of S1 and SCM
(OPEN)
• S1 and SCM short circuit lines are not
connected
• Malfunction caused by interference
• Hardware failure
• Poor connection of the IO card
• The IO card does not match the
version of the control board
• Reset the switch and cycle the power.
• Re-connect the short circuit lines
• Verify the wiring/grounding of the main circuit, control circuit and encoder to prevent interference.
• If S1 fault still exists after cycling the power, please return to the factory for repair.
• Check if the PIN of IO card is broken.
• Check if the IO card connects to the control board correctly, and if the screws are tightened well.
• For incorrect version, contact Technical Support.
Fault Display
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...