DRIVE CONFIGURATION
Default Settings Table - VFD Menu
51
*
If Motor Freq Sel [SET-06] is changed to 50 Hz, all output frequency related parameters are adjusted. Refer to
“Default Settings Table - Frequency Defaults with 50 Hz” on page 62
Default Settings Table - VFD Menu
Parameters in highlighted rows are reset when the application is changed
[SET–00]
.
SET-47 HLD Select
By Current By Current By Current By Current By Current
By Current
By Current By Current By Torque By Torque
SET-48 HLD Level
110%
110%
110%
110%
110%
110%
110%
150%
110%
110%
SET-49 HLD Frequency
20 Hz
20 Hz
20 Hz
20 Hz
20 Hz
30 Hz
20 Hz
20 Hz
60 Hz
40 Hz
SET-50 HLD Delay
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
5 Sec
2 Sec
SET-51
HLD Recovery T
0 Min
0 Min
0 Min
0 Min
0 Min
0 Min
0 Min
0 Min
0 Min
0 Min
SET-52 HLD Recover Cnt
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only Read Only Read Only
SET-53 ACC Change Freq
0 Hz
0 Hz
0 Hz
0 Hz
0 Hz
0 Hz
0 Hz
0 Hz
60 Hz
0 Hz
SET-54 Second ACC
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
5 Sec
60 Sec
SET-55 Second DEC
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
5 Sec
60 Sec
SET-56 ACC/DEC Hyster
0 Hz
0 Hz
0 Hz
0 Hz
0 Hz
1 Hz
0 Hz
0 Hz
1 Hz
0 Hz
SET-57 Display Line 1
Freq
Command
Freq
Command
Freq
Command
Freq
Command
Freq
Command
Freq
Command
Freq
Command
Freq
Command
Freq
Command
Freq
Command
SET-58 Display Line 3
PID
Feedback %
PID
Feedback %
PID
Feedback %
PID
Feedback %
PID
Feedback %
PID
Feedback %
PID
Feedback %
PID
Feedback %
PID
Feedback %
PID
Feedback %
SET-59 Keypad Freq
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
10 Hz
115 Hz
115 Hz
SET-60 HOA Mode Source
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
SET-61
KPD STOP as OFF
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
SET-62 Carrier Freq
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
SET-63 2/3-Wire Select
2-Wire
Fwd/Rev
2-Wire
Fwd/Rev
2-Wire
Fwd/Rev
2-Wire
Fwd/Rev
2-Wire
Fwd/Rev
2-Wire Fwd/
Rev
2-Wire
Fwd/Rev
2-Wire
Fwd/Rev
2-Wire
Fwd/Rev
2-Wire
Fwd/Rev
CODE
Display
Basic
Supply Fan Exhaust
Fan
Cooling
Tower
Centrifugal
Pump
Submersible
Pump
Vacuum
Pump
Constant
Torque
FE
MagForce PM Motor
CODE
Display
Basic
Supply Fan Exhaust
Fan
Cooling
Tower
Centrifugal
Pump
Submersible
Pump
Vacuum
Pump
Constant
Torque
FE MagForce PM Motor
VFD-00 VFD Max Freq
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
120 Hz
120 Hz
VFD-01
VFD Start Freq
0.50 Hz
0.50 Hz
0.50 Hz
0.50 Hz
0.50 Hz
0.50 Hz
0.50 Hz
0.50 Hz
0.50 Hz
0.50 Hz
VFD-02 VFD Base Freq
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
120 Hz
120 Hz
VFD-03 V/F Pattern
Linear
Linear
Linear
Linear
Linear
Linear
Linear
Linear
Linear
Linear
VFD-04 Step Freq-1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-05 Step Freq-2
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-06 Step Freq-3
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-07 Step Freq-4
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-08 Step Freq-5
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-09 Step Freq-6
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-10
Step Freq-7
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-11
Step Freq-8
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-12
Step Freq-9
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-13
Step Freq-10
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-14
Step Freq-11
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-15
Step Freq-12
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-16
Step Freq-13
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-17
Step Freq-14
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-18
Step Freq-15
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-19
ACC-2 Time
40 Sec
40 Sec
40 Sec
40 Sec
40 Sec
2 Sec
40 Sec
40 Sec
2 Sec
40 Sec
VFD-20 DEC-2 Time
40 Sec
40 Sec
40 Sec
40 Sec
40 Sec
2 Sec
40 Sec
40 Sec
2 Sec
40 Sec
VFD-21
ACC-3 Time
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
VFD-22 DEC-3 Time
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
VFD-23 ACC-4 Time
30 Sec
30 Sec
30 Sec
30 Sec
30 Sec
30 Sec
30 Sec
30 Sec
30 Sec
30 Sec
VFD-24 DEC-4 Time
40 Sec
40 Sec
40 Sec
40 Sec
40 Sec
40 Sec
40 Sec
40 Sec
40 Sec
40 Sec
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...