SPECIFICATIONS
200~230V Class 1~125HP (0.75~90kW)
236
200~230V Class 1~125HP (0.75~90kW)
(1)
UL Type 1 kit comes with UL Open Type VFD which are Frame D and larger.
(2)
The VFD cannot produce output voltage greater than input voltage.
(3)
Variable torque (VT) motor rating based on a 120% overload for 1 minute. Constant Torque (CT) motor rating based
on 120% overload for 1 minute and 160% overload for 3 seconds.
Model (CXD-xxx-2V)
UL Type 1
(1)
005A 007A 010A 015A 021A 031A 046A 061A 075A 090A 105A
146A
180A
215A 276A 322A
Frame Size
A
B
C
D
E
Input Ratings
Voltage
200 (-15%) to 240 VAC (+10 %)
Frequency
50/60 Hz (± 5%)
Current -
Variable Torque
6.4
9.6
15
22
25
50
65
83
100
116
146
180
215
276
322
-
Current -
Constant Torque
3.9
6.4
12
16
20
28
36
52
72
83
99
124
143
171
206
245
Output Ratings
Carrier Freq
2.0 - 15.0 kHz
2.0 - 10.0 kHz
2.0 - 9.0kHz
Voltage
(2)
200 ~ 240 VAC
(2)
Frequency
0.01 ~ 599 Hz
0.01 ~ 400 Hz
Efficiency
98%
Power Factor
>0.98
Weight kg (lbs.)
2.6 ± 0.3 (5.8 ± 0.7)
5.4 ± 1 (11.9 ± 2.2)
9.8 ± 1.5 (21.6 ± 3.3)
38.5 ± 1.5 (84.9 ± 3.3)
64.8 ± 1.5 (142.9 ± 3.3)
DC Choke
None
Built-in 3%
VFD Ratings with 3-Phase Input Power
Variable
Torque
Motor
(3)
Ratings
Max Amps
5
7.5
10
15
21
31
46
61
75
90
105
146
180
215
276
322
Capacity [kVA]
2
3
4
6
8.4
12
18
24
30
36
42
58
72
86
110
128
Max HP @ 200 V
Surface Motor
1
1.5
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
Max HP @ 208 V
Surface Motor
1
1.5
2
3
5
7.5
10
20
25
30
30
50
60
75
100
100
Max HP @ 230 V
Surface Motor
1
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
Max HP @ 200 V
4” Submersible
.75
1.5
2
3
5
7.5
–
–
–
–
–
–
–
–
–
–
Max HP @ 230 V
4” Submersible
1
1.5
2
3
5
7.5
–
–
–
–
–
–
–
–
–
–
Max HP @ 200 V
6” Submersible
–
–
–
–
5
7.5
10
15
20
25
30
40
40
60
–
–
Max HP @ 230 V
6” Submersible
–
–
–
–
5
7.5
10
20
20
25
30
40
50
60
–
–
Constant
Torque
Motor
(3)
Ratings
Max Amps
3
5
8
11
17
25
33
49
65
75
90
120
146
180
216
255
Capacity [kVA]
1.2
2
3.2
4.4
6.8
10
13
20
26
30
36
48
58
72
86
20
Max HP @ 200 V
.5
1
2
3
3
5
10
15
20
20
25
40
50
60
60
75
Max HP @ 230 V
.5
1
2
3
5
8
10
15
20
25
30
40
50
60
75
100
VFD Ratings with 1-Phase Input Power
Variable
Torque
Motor
Ratings
Max Amps
2.5
3.75
5
7.5
10.5
15.5
23
30.5
37.5
45
52.5
48.1
59.4
70.9
91
106.2
Max HP @ 200 V
Surface Motor
.5
.75
1
1
2
3
5
7.5
10
10
15
10
15
20
25
30
Max HP @ 208 V
Surface Motor
.5
.75
1
2
2
3
5
7.5
10
10
15
15
20
25
30
30
Max HP @ 230 V
Surface Motor
.5
.75
1
2
3
5
7.5
10
10
15
15
10
20
25
30
40
Max HP @ 200 V
4” Submersible
–
.5
.5
1.5
2
3
5
7.5
–
–
–
–
–
–
–
–
Max HP @ 230 V
4” Submersible
–
.5
1
1.5
2
3
5
7.5
–
–
–
–
–
–
–
–
Max HP @ 200 V
6” Submersible
–
–
–
–
–
–
5
7.5
10
10
10
10
15
20
25
30
Max HP @ 230 V
6” Submersible
–
–
–
–
–
–
5
7.5
10
10
15
15
20
20
25
33
Constant
Torque
Motor
Ratings
Max Amps
1.5
2.5
4
5.5
8.8
12.5
16.5
24.5
32.5
37.5
45
39.6
48.2
59.4
71
84.2
Max HP @ 200 V
0.25
.5
.75
1
2
3
3
5
10
10
10
10
10
15
20
25
Max HP @ 230 V
0.25
.5
.75
1
2
3
5
7.5
10
10
15
10
15
20
25
30
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...