PARAMETER REFERENCE TABLES
Parameter Descriptions > ADVANCE Menu
218
ADV-26 0794 Y Lead Freq Bump 0.0 to (
[SET-23]
*0.4 Hz)
PID Low Freq Limit increase value with
MMC Accel Time [ADV-27]
at Lag pump
stop to prevent system underpressure condition. This parameter is used for
[ADV-10]
selection
3_Lead-Lag MMC
control.
ADV-27 0795 Y MMC Accel Time 0 to 600 sec
Sets acceleration time for PID Low Frequency limit value change from
PID
Low Freq Limit [SET-22]
to (
PID Low Freq Limit [SET-22]
+
[ADV-26]
) at Lag pump stop.
ADV-28 0796 Y Power-On Delay 0 to 6000 sec
This timer provides run delay at VFD power-up with run command present
to prevent multiple starts during power surges.
ADV-29 0797 Y Run Delay Timer 0 to 6000 sec
This timer provides a delay at every VFD start when run command is
applied. Timer starts before every VFD start by run command, auto-restarts,
fault reset, sleep wake-up, etc.
FO (Fireman’s Override) mode will disable this timer.
ADV-30 0798 Y Backspin Timer
0 to 6000 sec
Duration after stop state that the drive disables output. Protects drive from
motor backspinning due to column of water backflowing through pump.
ADV-31 0799 Y Aux Timer Type 0_On-Delay
1_Off-Delay
2_One-Pulse
3_On-Pulser
4_Off-Pulser
Activates relay output based on selected Aux Timer input source and Timer
Type. Aux Timer will be enabled when any digital output is set to Aux Timer
Out.
0_On-Delay: When selected timer input is activated, the timer output relay
will be activated when timer expires. It will stay activated until Aux Timer
input is deactivated. This is the default setting.
1_Off-Delay: When selected timer input is activated, the Aux Timer output
will be activated. When Aux Timer input is deactivated, the timer will start
counting and its output will be activated when timer expires.
2_One-Pulse (on rising edge): When selected timer input is activated, the
Aux Timer output will be activated for duration of the Aux Timer whether
input is still active or not.
3_On-Pulser: When Aux Timer input is activated, the timer output will be
activated for duration of Aux Timer. Then timer output will be deactivated
for Aux Timer duration. Then timer output will be activated for Aux Timer
duration again. Aux Timer will provide symmetrical pulses until its input is
deactivated.
4_Off-Pulser: When Aux Timer input is activated, the timer output will stay
inactive for duration of Aux Timer. Then timer output will be activated for
Aux Timer duration. Then timer output will be deactivated for Aux Timer
duration again. Aux Timer will provide symmetrical pulses until its input is
deactivated.
NOTE:
Aux Timer does not use
DI NO/NC [IO-46]
settings.
ADV-32 0800 Y Aux Timer Time 0 to 6000 sec
Active or Inactive duration of relay.
ADV-33 0801 Y Aux Timer Input 0_D-Input MI1
1_D-Input MI2
2_D-Input MI3
3_D-Input MI4
4_D-Input MI5
5_D-Input MI6
6_D-Input MI7
7_D-Input MI8
8_D-Output R1
9_D-Output R2
10_D-Output R3
11_FWD DI
12_REV DI
Selects source to initiate Aux Timer operation. Default is
11_FWD DI
.
ADV-34 0802 Y Min Run Timer
0 to 6000 sec
Once drive starts motor, the motor continuously runs for this length of time
even though a stop command is present.
ADV-35 0803 N Multi-VFD Set
0_Single VFD
1_2 VFDs
2_3 VFDs
3_4 VFDs
4_5 VFDs
5_6 VFDs
6_7 VFDs
7_8 VFDs
This setting defines the number of drives in the system, including Lead, Lag,
Standby, and Jockey.
CODE Mod
Bus AR Display Name
Range
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...