MAINTENANCE
Troubleshooting
177
ECrF
(83)
ExCom Rtn def
Communication card returns to the default setting
Action and Reset
Action condition
Communication card returns to the default setting
Action time
N/A
Reset method
Automatically
Reset condition
Immediately
Recorded
N/A
Possible Causes
Corrective Action
• Communication card is returning to
default setting
• No actions necessary
Warning Display
Description
ECto
(81)
ExCom Intr T-out
Communication time-out for communication card and the upper unit
Action and Reset
Action condition
N/A
Action time
N/A
Reset method
Automatically
Reset condition
CMC-EC01: resets when the communication with the upper unit is back to normal
Recorded
N/A
Possible Causes
Corrective Action
• Communication card is not connected
with the upper unit
• Communication error of the upper unit
• Check if the connection of the communication cable is correct
• Check if the communication of the upper unit is normal
Warning Display
Description
ECtt
(72)
ExCom Test Mode
Communication card is in the test mode
Action and Reset
Action condition
Immediately
Action time
N/A
Reset method
Cycle the power and enter the normal mode
Reset condition
N/A
Recorded
N/A
Possible Causes
Corrective Action
• Communication command error
• Cycle the power
Warning Display
Description
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...