ADVANCED APPLICATION OPTIONS
Operation with Permanent Magnet Motors
98
Setup FE MagForce Pump Motor
Franklin Electric MagForce motors use an internal permanent magnet motor (IPM) design with 4-pole con
-
struction and synchronous speed. This means the electrical frequency is the same speed as the shaft speed
with no slip in the rotor. Since the motor has 4 poles, the electrical frequency running the motor will need to
be twice that of a 2-pole motor for same desired RPM.
FE MagForce motors are rated to operate up to 3600 RPM in North Amer
-
ica or 3000 RPM in the EU, and not to exceed the maximum SFA rating of
the motor. To run pumps at their rated speed, use the pump RPM calcula
-
tion “Poles x RPM / 120 = Electrical Frequency (Hz)” in order to set the
VFD Max Freq [VFD–00]
.
Use the following steps to configure an X-Drive for use with a FE MagForce:
Basic Setup
IMPORTANT:
If the VFD has been used in a previous application, the drive parameters should be completely
reset using
Parameter Reset [ADV–03]
, option
4_Reset all Param
.
1.
Application [SET–00]:
Set to option
8_FE MagForce
. This selection assumes the use of a 4-pole, 3-phase
PM motor running at 120 Hz and automatically updates all relevant parameters to the proper defaults.
IMPORTANT:
The FE MagForce application should only be used with Franklin Electric MagForce motors.
Do not use this selection with other permanent magnet motors.
2.
Input Phase [SET–01]:
Verify that the setting matches the
type of power supply. Default = 3-phase.
3.
Motor Horsepower [SET–02]:
Enter the maximum rated
horsepower from the motor nameplate.
4.
Motor FLA (SFA) [SET–03]:
Set to the current rating on the
nameplate associated with the power rating of the pump.
5.
Motor RPM [SET–04]:
Enter the rated motor RPM from the
motor nameplate.
6.
Motor Voltage [SET–05]:
Enter the rated voltage from the
motor nameplate.
7.
VFD Max Freq [VFD–00]:
The highest frequency allow
-
able. This should be set to the calculated electrical fre
-
quency corresponding to the target pump RPM in the table
above.
8.
VFD Base Freq [VFD–02]:
This should be set to the motor nameplate frequency rating.
9.
Carrier Freq [SET–62]:
This should be set to 4 kHz for sine filters and 2 kHz for dV/dt filters.
Permanent Magnet Specific Parameters
For FE MagForce applications, the drive automatically sets:
•
Control Method [Motor–05]:
This should be
2_Sensorless
Vector Control.
•
Motor Type [Motor–06]:
This should be
2_PM-IPM
.
•
Motor Poles [Motor–07]:
This should be
4
for a FE MagForce motor.
•
PM Inertia [Motor–08]:
This value is automatically calculated.
Pump RPM
Electrical Frequency
3600
4 x 3600 / 120 = 120 Hz
3450
4 x 3450 / 120 = 115 Hz
3525
4 x 3525 / 120 = 117.5 Hz
3000
4 x 3000 / 120 = 100 Hz
2850
4 x 2850 / 120 = 95 Hz
2938
4 x 2938 / 120 = 98 Hz
8
4
6
5
3
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...