Run Command examples using one program
Example 1: Scheduled Run command is active from 5am to 1pm every Monday
•
Prog-1 Setting [ADV-56]:
1_VFD Run
•
Prog-1 On Time [ADV-57]:
05:00
•
Prog-1 Off Time [ADV–58]:
13:00
•
Prog-1 Week Day [ADV-59]:
_M_____
Example 2: Scheduled Run command is activated on Monday 13:00 until next Monday 00:05AM.
•
Prog-1 Setting [ADV-56]:
1_VFD Run
•
Prog-1 On Time [ADV-57]:
13:00
•
Prog-1 Off Time [ADV–58]:
05:00
•
Prog-1 Week Day [ADV-59]:
_M_____
Example 3: Run enable is never active (program is disabled).
•
Prog-1 Setting [ADV-56]:
1_VFD Run
•
Prog-1 On Time [ADV-57]:
13:00
•
Prog-1 Off Time [ADV–58]:
13:00
•
Prog-1 Week Day [ADV-59]:
_M_____
Scheduling example using three programs
In this example, we want to schedule three programs to have the VFD accomplish the following:
1.
Set VFD Start at 6:00 (6AM) and VFD Stop at 23:00 (11PM) during work days (Mon, Tue, Wed, Thu, Fri)
2. Have the VFD change from No-PID speed reference (keypad, analog input or Comms) every work day
to preset
Step Frequency-1 [VFD-04]
from 11:00 (11AM) to 17:00 (5PM)
3. Have the VFD change from No-PID speed reference on Monday and Friday to
Step Frequency-2 [VFD-05]
from 15:00 (3PM) to 19:00 (7PM).
1st Program Parameters:
•
Prog-1 Setting [ADV-56]:
1_VFD Run
•
Prog-1 On Time [ADV-57]:
06:00
•
Prog-1 Off Time [ADV–58]:
23:00
•
Prog-1 Week Day [ADV-59]:
_MTWTF_
2nd ProgramParameters:
•
Prog-2 Setting [ADV–60]:
2_Step Freq-1
•
Prog-2 On Time [ADV-61]:
11:00
•
Prog-2 Off Time [ADV-62]:
17:00
•
Prog-2 Week Day [ADV–63]:
_MTWTF_
3rd Program Parameters:
•
Prog-3 Setting [ADV-64]:
3_Step Freq-2
•
Prog-3 On Time [ADV-65]:
15:00
•
Prog-3 Off Time [ADV-66]:
19:00
•
Prog-3 Week Day [ADV-67]:
_M____F_
Run
Enable
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Run
Enable
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Run
Enable
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Run enable is never active
Scheduling Example
MON
TUE
WED
THU
FRI
VFD RUN
Speed-B
Speed-A
Keypad Hz
06:00
23:00
06:00
23:00
06:00
23:00
06:00
23:00
06:00
23:00
SAT
Time/Days
19:00
15:00
17:00
11:00
17:00
11:00
17:00
11:00
17:00
11:00
19:00
15:00
17:00
11:00
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...