Aquastorm 200
1-24 Overview
3.3
ELECTRICAL REQUIREMENTS
Standard Electrical Configuration:
460 VAC, 3 PH, 60 Hz (290 Amps Max.)
Optional Electrical Configuration:
220 VAC, 3 PH, 60 Hz (600 Amps Max.)
380 VAC, 3 PH, 50 Hz (400 Amps Max.)
Reference Schematics
VOLTAGE
DRAWING #
460V, 60Hz
8-1679-006-02-2
220V, 60Hz
8-1679-005-01-2
380V, 50Hz
8-1679-008-03-2
Panel Layout
8-1679-007-01-2
Power
Standard electrical voltage is 460 VAC, 3 phase, 60 Hz. (214 Amps Max.)
To calculate FLA (Full Load Amps) for specific system configuration, use the following formula and the KVA
ratings specific per module provide below:
Amps Required =
Total machine kVA x 1000
(1.732) (Machine Voltage)
NOTE
The normal operating power is 80 - 85% of the maximum power required, depending on
process parameters and operational load for the product being run.
Aquastorm 200™ Modules
Module
Total Power
Controls
3 kVA
Wash Module
Heaters (2 @ 16 kVA) 32 kVA
5 HP Pump (Std.)
5 kVA
10 HP Pump (Opt.)
10 kVA
Chemical Isolation Level 1 (Opt.)
7.5 HP Blower (Std.) 7.7 kVA
Enhanced Chemical Isolation Level 2
(Opt.)
7.5 HP Blower (Std.) 7.7 kVA
Enhanced Chemical Isolation Level 3
(Opt.)
7.5 HP Blower (Std.) 7.7 kVA
Single 16kVA Heater (Std.)
16
kVA
Rinse Module
Heaters (2 @ 16 kVA) 32 kVA
5 HP Pump (Std.)
5 kVA
10 HP Pump (Opt.)
10 kVA
Dryer Module #1
7.5 HP Blower (Std.) 7.7 kVA
10 HP Blower (Opt.) 10 kVA
15 HP Blower (Opt.) 14.6 kVA
Dryer Module #2
7.5 HP Blower (Std.) 7.7 kVA
10 HP Blower (Opt.) 10 kVA
IR Heaters (Opt.)
3.6 kVA
Add-On Single Dryer (Opt.)
7.5 HP Blower (Std.) 7.7 kVA
10 HP Blower (Opt.) 10 kVA
15 HP Blower (Opt.) 14.6 kVA
Add-On Dual Dryer (Opt.)
Dual Dryer Module #1
7.5 HP Blower (Std.) 7.7 kVA
10 HP Blower (Opt.) 10 kVA
15 HP Blower (Opt.) 14.6 kVA
Dual Dryer Module #2
7.5 HP Blower (Std.) 7.7 kVA
10 HP Blower (Opt.) 10 kVA
IR Heaters (Opt.)
3.6 kVA
3
/
4
HP Sump Pump (Opt.)
.83
kVA
2 HP Treatment Interface
Pump (Opt.)
2.2 kVA
Enclosed CLS (closed loop system) (Opt.)
NOTE
Separate power drop required for
this feature; standard power is 460
VAC, 3 phase.
Module
Total Power
Heater (Std.)
30 kVA
Summary of Contents for Aquastrom 200