7.9 Errors related to stopped background task T_SWIFTI_LED
Description
Execution errors are reported because the background task T_SWIFTI_LED is
stopped.
Consequences
Program execution is halted.
Possible causes
The I/O module is changed or reset.
Recommended actions
1 Tap
I/O
in the main page of the FlexPendant.
2 Check the device status, whether the
CabinetIO
device with address
192.168.125.100
is in
Not connected
state, and there is another device in
Unknown
state.
3 If in previous situation, tap the menu button after the unknown device and
tap
Identify
in the list.
Verify whether the unknown device is the I/O module installed on the
controller. If yes, the LED blinks on the I/O module.
4 Tap
Configure
in the list for the unknown device.
5 In the displayed
I/O Modernization
window, choose
Update device
in the
Configuration
area and select
CabinetIO
from the drop-down list.
This will update the unknown device to CabinetIO.
6 Tap
Apply
.
7 Restart the controller.
The system works normally.
Product manual - CRB 1100
693
3HAC078007-001 Revision: J
© Copyright 2021-2023 ABB. All rights reserved.
7 Troubleshooting
7.9 Errors related to stopped background task T_SWIFTI_LED
Summary of Contents for CRB 1100
Page 1: ...ROBOTICS Product manual CRB 1100 ...
Page 162: ...This page is intentionally left blank ...
Page 184: ...This page is intentionally left blank ...
Page 652: ...This page is intentionally left blank ...
Page 698: ...This page is intentionally left blank ...
Page 712: ...This page is intentionally left blank ...
Page 714: ...This page is intentionally left blank ...
Page 719: ......