Configuring the laser scanner
Protection fields
Four protection fields are defined to provide a progressive safety protection. The
following figure illustrates the field ranges.
A
B
C
D
xx2100000165
Description
Lamp col-
or
Device
mapping
(default)
Field
The warning area field defines the largest
range, but it shall be within the scanning
range of the scanner.
Yellow
65
WarningArea
A
Within in this field range, the lamp unit on
the process hub lights up yellow, and the
robot movement speed reduces to a lower
speed that is set by the user.
Within in this field range, the lamp unit still
lights up yellow, but Tool Speed Supervi-
sion (TSP) is enabled. If the robot moves
in the speed that is out of the defined
range for TSP, the motor is off.
Yellow
67
WarningAreaTSP
B
For details about TSP, see
Application
manual - Functional safety and SafeMove
.
Within this field range, the lamp unit turns
to red and the robot movement speed is
reduced to 0. The robot stands still.
Red
64
ProtectingArea
C
Continues on next page
Product manual - CRB 1100
121
3HAC078007-001 Revision: J
© Copyright 2021-2023 ABB. All rights reserved.
3 Installation and commissioning
3.7.5.1 Configuration of one PROFINET-base laser scanner (RobotWare 7.5 or earlier)
Continued
Summary of Contents for CRB 1100
Page 1: ...ROBOTICS Product manual CRB 1100 ...
Page 162: ...This page is intentionally left blank ...
Page 184: ...This page is intentionally left blank ...
Page 652: ...This page is intentionally left blank ...
Page 698: ...This page is intentionally left blank ...
Page 712: ...This page is intentionally left blank ...
Page 714: ...This page is intentionally left blank ...
Page 719: ......