2 Parameters
2.2 List of parameters
SINAMICS DCP
244
List Manual (LH21), 05/2016
Dependency:
The parameter is only valid for the following temperature sensors with a continuous characteristic:
- KTY84 (p50490 = 1)
- PT100 (p50490 = 6).
- NTC thermistor K227 (p50490 = 7)
- PT1000 (p50490 = 8)
Description:
Sets the fault threshold for monitoring the external temperature (terminal X177.53-55).
Dependency:
The parameter is only valid for the following temperature sensors with a continuous characteristic:
- KTY84 (p50490 = 1)
- PT100 (p50490 = 6).
- NTC thermistor K227 (p50490 = 7)
- PT1000 (p50490 = 8)
Description:
Sets the type for analog input 0 (AI 0, X177.25/26) on the CUD.
Value:
0:
Bipolar voltage input (-10 V ... +10 V)
1:
Bipolar current input (-20 mA ... +20 mA)
2:
Unipolar current input monitored (+4 mA ... +20 mA)
Note:
AI: Analog Input
Description:
Sets the scaling for analog input 0 (AI 0, X177.25/26) on the CUD.
The value indicates the percentage value for mapping an input voltage of 10 V or an input current of 20 mA at the
analog input.
Example:
p50701 = 90%
--> 10 V or 20 mA is scaled to 90%
--> 5 V or 10 mA is equivalent to 45%
Note:
AI: Analog Input
Description:
Sets the offset for analog input 0 (AI 0, X177.25/26) on the CUD.
Note:
AI: Analog Input
p50492
Temperature monitoring external fault threshold / Ext temp F thresh
DCP_CTRL
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
8030
Min Max
Factory
setting
0 [°C]
200 [°C]
0 [°C]
p50700
CUD analog input 0 type / CUD AI 0 type
DCP_CTRL
Can be changed:
T
Access level:
3
Data type:
Integer16
Func. diagram:
2075
Min Max
Factory
setting
0 2
0
p50701[0...n]
CUD analog input 0 scaling / CUD AI 0 scal
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
2075
Min Max
Factory
setting
-1000.0 [%]
1000.0 [%]
100.0 [%]
p50702
CUD analog input 0 offset / CUD AI 0 offs
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
2075
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
0.00 [%]
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...