2 Parameters
2.2 List of parameters
SINAMICS DCP
66
List Manual (LH21), 05/2016
Description:
Sets the serial interface for the debug monitor.
With p2039 = 1, the serial interface COM2 (X179) is set.
Other values are not permitted.
Description:
Sets the monitoring time to monitor the process data received via the fieldbus interface.
If no process data is received within this time, then an appropriate message is output.
Dependency:
Refer to: F01910
Note:
p2040 = 0:
Monitoring is de-activated.
Description:
Sets the PROFIBUS Ident Number (PNO-ID).
SINAMICS can be operated with various identities on PROFIBUS. This allows the use of a PROFIBUS GSD that is
independent of the device (e.g. PROFIdrive VIK-NAMUR with Ident Number 3AA0 hex).
Value:
0:
SINAMICS
1:
VIK-NAMUR
Note:
Every change only becomes effective after a POWER ON.
Description:
Displays the PROFIdrive PZD state.
Dependency:
Refer to: p2044
Note:
When using the "setpoint failure" signal, the bus can be monitored and an application-specific response triggered
when the setpoint fails.
Description:
Sets the delay time to initiate fault F01910 after a setpoint failure.
The time until the fault is initiated can be used by the application. This means that is is possible to respond to the
failure while the drive is still operational (e.g. emergency retraction).
p2039
Select debug monitor interface / Debug monit select
CU_DCP
Can be changed:
U, T
Access level:
4
Data type:
Unsigned16
Func. diagram:
-
Min Max
Factory
setting
0 3
1
p2040
Fieldbus interface monitoring time / Fieldbus t_monit
CU_DCP
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
9310
Min Max
Factory
setting
0 [ms]
1999999 [ms]
100 [ms]
p2042
PROFIBUS Ident Number / PB Ident No.
CU_DCP
Can be changed:
T
Access level:
3
Data type:
Integer16
Func. diagram:
-
Min Max
Factory
setting
0 1
0
r2043.0...2
BO: IF1 PROFIdrive PZD state / IF1 PD PZD state
CU_DCP
Can be changed:
-
Access level:
3
Data type:
Unsigned8
Func. diagram:
2410
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Setpoint failure
Yes
No
-
02
Fieldbus oper
Yes
No
-
p2044
IF1 PROFIdrive fault delay / IF1 PD fault delay
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
2410
Min Max
Factory
setting
0 [s]
100 [s]
1 [s]
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...