2 Parameters
2.2 List of parameters
SINAMICS DCP
306
List Manual (LH21), 05/2016
Description:
Displays the actual value of the current at side 2.
Dependency:
Refer to: r55542
Description:
Sets the offset for the "local" adjustment of the voltage actual value.
Index 0:
Adjustment of the voltage actual value at side 1
Index 1:
Adjustment of the voltage actual value at side 2
Index:
[0] = Side 1
[1] = Side 2
Description:
Sets the gain for the "local" adjustment of the voltage actual value.
Index 0:
Adjustment of the voltage actual value at side 1
Index 1:
Adjustment of the voltage actual value at side 2
Index:
[0] = Side 1
[1] = Side 2
Description:
Display and BICO output for the status of the power unit monitoring.
r55544
Actual value current side 2 / Act val I_S2
DCP_CTRL
Can be changed:
-
Access level:
1
Data type:
FloatingPoint32
Func. diagram:
6850
Min Max
Factory
setting
- [A]
- [A]
- [A]
p55545[0...1]
Actual value voltage offset adjustment / ActVal U offs adj
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
6850
Min Max
Factory
setting
-5.00 [%]
5.00 [%]
0.00 [%]
p55546[0...1]
Actual value voltage gain adjustment / ActVal U gain adj
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
6850
Min Max
Factory
setting
-5.00 [%]
5.00 [%]
0.00 [%]
r55550.0...15
CO/BO: Power unit monitoring status / PU monit status
DCP_CTRL
Can be changed:
-
Access level:
2
Data type:
Unsigned16
Func. diagram:
6855
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
IGBT1 desaturation occurred
Yes
No
6855
01
IGBT2 desaturation occurred
Yes
No
6855
02
IGBT3 desaturation occurred
Yes
No
6855
03
IGBT4 desaturation occurred
Yes
No
6855
04
IGBT5 desaturation occurred
Yes
No
6855
05
IGBT6 desaturation occurred
Yes
No
6855
06
IGBT7 desaturation occurred
Yes
No
6855
07
IGBT8 desaturation occurred
Yes
No
6855
08
Overcurrent has occurred in power unit 1
Yes
No
6855
09
Overcurrent has occurred in power unit 2
Yes
No
6855
10
Overvoltage has occurred at side 1.
Yes
No
6855
11
Overvoltage has occurred at side 2.
Yes
No
6855
12
Overtemperature has occurred at the AC
Yes
No
6855
13
Overtemperature has occurred at the BD
Yes
No
6855
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...