2 Parameters
2.2 List of parameters
SINAMICS DCP
32
List Manual (LH21), 05/2016
h = reserved
if the value 0 is displayed in all indices, then components are not detected via DRIVE-CLiQ.
If a value F hex occurs at a position of the coding (abcd efgh hex), then an overflow has occurred.
Description:
Sets the device target topology in coded form (refer to r0098). The setting is made during commissioning.
De-activated or non-available components are also counted
Index:
[0] = DRIVE-CLiQ socket X100
[1] = DRIVE-CLiQ socket X101
[2...5] = Reserved
Dependency:
The parameter can only be written into for p0097 = 0.
To perform an automatic device configuration run, an index of the device target topology must be set to the value of
the device actual topology in r0098 for acknowledgement. An index of the device actual topology with a value other
than 0 must be selected.
Refer to: p0097, r0098
Refer to: A01330
Note:
The parameter can only be set to the values 0, the value of the actual device topology, the value of the actual device
target topology and FFFFFFFF hex.
If the value 0 is displayed in all of the indices, then the system has still not been commissioned.
The value FFFFFFFF hex indicates that the topology was not generated by the automatic device configuration but
was commissioned using the commissioning software (e.g. using parameter download).
Description:
The parameter contains the object number via which every drive object can be addressed.
The number of an existing drive object is entered into each index.
Value = 0: No drive object is defined.
Note:
The numbers are automatically allocated.
For the commissioning software, this object number cannot be entered using the expert list, but is automatically
assigned when inserting an object.
Description:
Displays the number of existing or existing and prepared drive objects.
Index:
[0] = Existing drive objects
[1] = Existing and prepared drive objects
Dependency:
Refer to: p0101
Note:
The numbers of the drive objects are in p0101.
Index 0:
Displays the number of drive objects that have already been set up.
Index 1:
Displays the number of drive objects that have already been set up and, in addition, the drive objects that still have to
be set up.
p0099[0...5]
Device target topology / Device_target topo
CU_DCP
Can be changed:
C1(1)
Access level:
1
Data type:
Unsigned32
Func. diagram:
-
Min Max
Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
p0101[0...n]
Drive object numbers / DO numbers
CU_DCP
Can be changed:
C1(1)
Access level:
2
Data type:
Unsigned16
Func. diagram:
-
Min Max
Factory
setting
0 62
0
r0102[0...1]
Number of drive objects / DO count
CU_DCP
Can be changed:
-
Access level:
2
Data type:
Unsigned16
Func. diagram:
-
Min Max
Factory
setting
- -
-
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...