2 Parameters
2.2 List of parameters
SINAMICS DCP
104
List Manual (LH21), 05/2016
Description:
Sets the message type for the selected fault or alarm.
Value:
1:
Fault (F)
2:
Alarm (A)
3:
No message (N)
Dependency:
Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2118
Note:
Re-parameterization is also possible if a message is present. The change only becomes effective after the message
has gone.
The message type can only be changed for messages with the appropriate identification (exception, value = 0).
Example:
F12345(A) --> Fault F12345 can be changed to alarm A12345.
In this case, the message number that may be possibly entered in p2100[0...19] and p2126[0...19] is automatically
removed.
Description:
Sets the message type for the selected fault or alarm.
Value:
1:
Fault (F)
2:
Alarm (A)
3:
No message (N)
Dependency:
Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2118
Note:
Re-parameterization is also possible if a message is present. The change only becomes effective after the message
has gone.
The message type can only be changed for messages with the appropriate identification (exception, value = 0).
Example:
F12345(A) --> Fault F12345 can be changed to alarm A12345.
In this case, the message number that may be possibly entered in p2100[0...19] and p2126[0...19] is automatically
removed.
Description:
Displays the sum of all of the fault and alarm buffer changes in the drive unit.
Dependency:
Refer to: r0944, r2121
Description:
This counter is incremented every time the alarm buffer changes.
Dependency:
Refer to: r2110, r2122, r2123, r2124, r2125
p2119[0...19]
Change message type type / Change type type
CU_DCP, DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
Integer16
Func. diagram:
8075
Min Max
Factory
setting
1 3
1
p2119[0...19]
Change message type type / Change type type
TM150, TM15DI_DO,
TM31
Can be changed:
U, T
Access level:
3
Data type:
Integer16
Func. diagram:
8050, 8075
Min Max
Factory
setting
1 3
1
r2120
CO: Sum of fault and alarm buffer changes / Sum buffer changed
All objects
Can be changed:
-
Access level:
4
Data type:
Unsigned16
Func. diagram:
8065
Min Max
Factory
setting
- -
-
r2121
CO: Counter alarm buffer changes / Alrm buff changed
All objects
Can be changed:
-
Access level:
3
Data type:
Unsigned16
Func. diagram:
8065
Min Max
Factory
setting
- -
-
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...