SINAMICS DCP
List Manual (LH21), 05/2016
141
2 Parameters
2.2 List of parameters
Description:
Sets the scaling characteristic for the analog outputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 1st value pair of the characteristic.
Index:
[0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency:
Refer to: p4076
Notice:
This parameter is automatically overwritten when changing p4076 (type of analog outputs).
Note:
The parameters for the characteristic do not have a limiting effect.
Description:
Sets the scaling characteristic for the analog outputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 1st value pair of the
characteristic.
Index:
[0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency:
The unit of this parameter (V or mA) depends on the analog output type.
Refer to: p4076
Notice:
This parameter is automatically overwritten when changing p4076 (type of analog outputs).
Note:
The parameters for the characteristic do not have a limiting effect.
Description:
Sets the scaling characteristic for the analog outputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency:
Refer to: p4076
Notice:
This parameter is automatically overwritten when changing p4076 (type of analog outputs).
Note:
The parameters for the characteristic do not have a limiting effect.
Description:
Sets the scaling characteristic for the analog outputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 2nd value pair of the
characteristic.
p4077[0...1]
TM31 analog outputs characteristic value x1 / TM31 AO char x1
TM31
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
9572
Min Max
Factory
setting
-1000.00 [%]
1000.00 [%]
0.00 [%]
p4078[0...1]
TM31 analog outputs characteristic value y1 / TM31 AO char y1
TM31
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
9572
Min Max
Factory
setting
-20.000 [V]
20.000 [V]
0.000 [V]
p4079[0...1]
TM31 analog outputs characteristic value x2 / TM31 AO char x2
TM31
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
9572
Min Max
Factory
setting
-1000.00 [%]
1000.00 [%]
100.00 [%]
p4080[0...1]
TM31 analog outputs characteristic value y2 / TM31 AO char y2
TM31
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
9572
Min Max
Factory
setting
-20.000 [V]
20.000 [V]
10.000 [V]
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...