4 Faults and alarms
4.2 List of faults and alarms
25: Analog input 4 (X177.3/4), voltage input, incorrect offset value
26: Analog input 4 (X177.3/4), voltage input, +10 V incorrect value
27: Analog input 4 (X177.3/4), voltage input, -10 V incorrect value
28: Analog input 4 (X177.3/4), voltage input, reference value incorrect
29: Analog input 5 (X177.5/6), voltage input, incorrect offset value
30: Analog input 5 (X177.5/6), voltage input, +10 V incorrect value
31: Analog input 5 (X177.5/6), voltage input, -10 V incorrect value
32: Analog input 5 (X177.5/6), voltage input, reference value incorrect
33: Analog input 6 (X177.7/8), voltage input, incorrect offset value
34: Analog input 6 (X177.7/8), voltage input, +10 V incorrect value
35: Analog input 6 (X177.7/8), voltage input, -10 V incorrect value
36: Analog input 6 (X177.7/8), voltage input, reference value incorrect
37: Analog input XT1.103/104, voltage input, incorrect offset value
38: Analog input XT1.103/104, voltage input, +25 V incorrect value
39: Analog input XT1.103/104, voltage input, -25 V incorrect value
40: Analog input XT1.103/104, voltage input, incorrect reference value
41: Analog input XT1.103/104, voltage input, incorrect offset value
42: Analog input XT1.103/104, voltage input, +80 V incorrect value
43: Analog input XT1.103/104, voltage input, -80 V incorrect value
44: Analog input XT1.103/104, voltage input, incorrect reference value
45: Analog input XT1.103/104, voltage input, incorrect offset value
46: Analog input XT1.103/104, voltage input, +270 V incorrect value
47: Analog input XT1.103/104, voltage input, -270 V incorrect value
48: Analog input XT1.103/104, voltage input, incorrect reference value
49: Analog output 0 (X177.49/50), incorrect offset value
50: Analog output 0 (X177.49/50), -10 V incorrect value
51: Analog output 0 (X177.49/50), +10 V incorrect value
52: Analog output 0 (X177.49/50), incorrect reference value
53: Analog output 1 (X177.51/52), incorrect offset value
54: Analog output 1 (X177.51/52), -10 V incorrect value
55: Analog output 1 (X177.51/52), +10 V incorrect value
56: Analog output 1 (X177.51/52), incorrect reference value
Note:
r50047[1]: Incorrect calibration value
Remedy:
Send the device to an authorized repair shop.
F60064 (N, A)
Error communicating with second processor TMS320
Drive object:
DCP_CTRL
Cause:
Communication with the second processor (TMS320) has failed.
Note:
r50047[1]: Communication counter in send direction
r50047[2]: Communication counter in receive direction
Remedy:
- carry out a POWER ON (power off/on).
- if necessary, send the device to an authorized repair shop.
F60065 (N, A)
Software update for second processor (TMS320) failed
Drive object:
DCP_CTRL
Cause:
Software update of the TMS320 processor on the CUD not successful.
Fault value (r0949, interpret decimal):
1: The TMS320 does not respond.
2: The TMS320 cannot be released (memory is password-protected).
3: Incompatible version of the bootloader software.
4: Incompatible version of the application software.
5: Error when deleting the TMS320 flash memory.
6: Error when programming the TMS320 flash memory.
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...