2 Parameters
2.2 List of parameters
SINAMICS DCP
152
List Manual (LH21), 05/2016
Description:
Display and binector output for the status for the Terminal Module 150 (TM150).
Dependency:
Refer to: p4102, p4103, r4105, p4118
Description:
Display and binector output for the status for the Terminal Module 31 (TM31).
Dependency:
Refer to: p4102
Description:
Displays the temperature actual value for the Terminal Module 150 (TM150)
Index:
[0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
[6] = Temperature channel 6
[7] = Temperature channel 7
r4104.0...23
BO: TM150 temperature evaluation status / TM150 temp status
TM150
Can be changed:
-
Access level:
1
Data type:
Unsigned32
Func. diagram:
9626, 9627
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Channel 0 alarm present
Yes
No
9626
01
Channel 0 fault present
Yes
No
9626
02
Channel 1 alarm present
Yes
No
9626
03
Channel 1 fault present
Yes
No
9626
04
Channel 2 alarm present
Yes
No
9626
05
Channel 2 fault present
Yes
No
9626
06
Channel 3 alarm present
Yes
No
9626
07
Channel 3 fault present
Yes
No
9626
08
Channel 4 alarm present
Yes
No
9626
09
Channel 4 fault present
Yes
No
9626
10
Channel 5 alarm present
Yes
No
9626
11
Channel 5 fault present
Yes
No
9626
12
Channel 6 alarm present
Yes
No
9627
13
Channel 6 fault present
Yes
No
9627
14
Channel 7 alarm present
Yes
No
9627
15
Channel 7 fault present
Yes
No
9627
16
Channel 8 alarm present
Yes
No
9627
17
Channel 8 fault present
Yes
No
9627
18
Channel 9 alarm present
Yes
No
9627
19
Channel 9 fault present
Yes
No
9627
20
Channel 10 alarm present
Yes
No
9627
21
Channel 10 fault present
Yes
No
9627
22
Channel 11 alarm present
Yes
No
9627
23
Channel 11 fault present
Yes
No
9627
r4104.0...1
BO: TM31 temperature evaluation status / TM31 temp status
TM31
Can be changed:
-
Access level:
1
Data type:
Unsigned16
Func. diagram:
9549, 9576
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Alarm is present
Yes
No
-
01
Fault is present
Yes
No
-
r4105[0...11]
CO: TM150 temperature actual value / TM150 temp_act val
TM150
Can be changed:
-
Access level:
1
Data type:
FloatingPoint32
Func. diagram:
9626, 9627
Min Max
Factory
setting
- [°C]
- [°C]
- [°C]
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...