4 Faults and alarms
4.2 List of faults and alarms
A02059
Trace: Time slice clock cycle for 2 x 8 recording channels not valid
Drive object:
All objects
Cause:
The selected time slice clock cycle cannot be used for more than 4 recording channels.
See also: p4723 (Trace time slice cycle)
Remedy:
Enter the clock cycle of an existing time slice with a cycle time >= 4 ms or reduce the number of recording channels
to 4 per trace.
The existing time slices can be read out via p7901.
A02060
Trace: Signal to be traced missing
Drive object:
All objects
Cause:
- a signal to be traced was not specified.
- the specified signals are not valid.
See also: p4730 (Trace record signal 0), p4731 (Trace record signal 1), p4732 (Trace record signal 2), p4733 (Trace
record signal 3)
Remedy:
- specify the signal to be traced.
- check whether the relevant signal can be traced.
A02061
Trace: Invalid signal
Drive object:
All objects
Cause:
- the specified signal does not exist.
- the specified signal can no longer be traced (recorded).
See also: p4730 (Trace record signal 0), p4731 (Trace record signal 1), p4732 (Trace record signal 2), p4733 (Trace
record signal 3)
Remedy:
- specify the signal to be traced.
- check whether the relevant signal can be traced.
A02062
Trace: Invalid trigger signal
Drive object:
All objects
Cause:
- a trigger signal was not specified.
- the specified signal does not exist.
- the specified signal is not a fixed-point signal.
- the specified signal cannot be used as a trigger signal for the trace.
See also: p4711 (Trace trigger signal)
Remedy:
Specify a valid trigger signal.
A02063
Trace: Invalid data type
Drive object:
All objects
Cause:
The specified data type to select a signal using a physical address is invalid.
See also: p4711 (Trace trigger signal), p4730 (Trace record signal 0), p4731 (Trace record signal 1), p4732 (Trace
record signal 2), p4733 (Trace record signal 3)
Remedy:
Use a valid data type.
A02070
Trace: Parameter cannot be changed
Drive object:
All objects
Cause:
The trace parameter settings cannot be changed when the trace is active.
See also: p4700, p4710, p4711, p4712, p4713, p4714, p4715, p4716, p4720, p4721, p4722, p4730, p4731, p4732,
p4733, p4780, p4781, p4782, p4783, p4789, p4795
Remedy:
- stop the trace before parameterization.
- if required, start the trace.
A02075
Trace: Pretrigger time too long
Drive object:
All objects
Cause:
The selected pretrigger time must be shorter than the trace time.
See also: p4721 (Trace recording time), p4722 (Trace trigger delay)
Remedy:
Check the pretrigger time setting and change if necessary.
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...