SINAMICS DCP
List Manual (LH21), 05/2016
285
2 Parameters
2.2 List of parameters
Description:
Display and connector output for the instantaneous maximum permissible current setpoint.
This is either the rated current, the short-time current or the base load current.
The value displayed here acts as upper current limit.
Description:
Display and connector output for various calculated power losses.
Index:
[0] = Power loss at IGBT T1A
[1] = Power loss at IGBT T1B
[2] = Power loss at IGBT T2A
[3] = Power loss at IGBT T2B
[4] = Power loss at free-wheeling diode D1A
[5] = Power loss at free-wheeling diode D1B
[6] = Power loss at free-wheeling diode D2A
[7] = Power loss at free-wheeling diode D2B
[8] = Total power loss in the power unit
Note:
For index 0 ... 7:
These power losses refer to a component.
For index 8:
Total power loss in the power unit = sum of the power losses for all components x number of B6 bridges.
30 kW device: 2 B6 bridges
120 kW device: 3 B6 bridges
Description:
Display and BICO output for the state of the dynamic overload.
Description:
Sets the permissible overload time for the dynamic overload.
Dependency:
Refer to: F60530
Note:
Fault F60530 is initiated if the duration of the maximum permissible overload current exceeds the time set here.
r55083
CO: Dynamic overload current limit / Dyn overld I_lim
DCP_CTRL
Can be changed:
-
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
6808
Min Max
Factory
setting
- [%]
- [%]
- [%]
r55084[0...8]
CO: Dynamic overload power loss calculated / Dyn overld P_loss
DCP_CTRL
Can be changed:
-
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
6808
Min Max
Factory
setting
- [W]
- [W]
- [W]
r55085.0...1
CO/BO: Dynamic overload state / Dyn overld state
DCP_CTRL
Can be changed:
-
Access level:
3
Data type:
Unsigned16
Func. diagram:
6808
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Threshold for maximum barrier layer
temperature exceeded
Yes
No
6808
01
Conditions for alarm A60039 fulfilled
Yes
No
6808
p55090
Dynamic overload load cycle overload time / DynOverld t_overld
DCP_CTRL
Can be changed:
U, T
Access level:
4
Data type:
FloatingPoint32
Func. diagram:
6008
Min Max
Factory
setting
1.00 [%]
300.00 [%]
60.00 [%]
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...