4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
442
List Manual (LH21), 05/2016
F07220 (N, A)
Drive: Master control by PLC missing
Drive object:
DCP_CTRL
Cause:
The "master control by PLC" signal was missing in operation.
- interconnection of the binector input for "master control by PLC" is incorrect (p0854).
- the higher-level control has withdrawn the "master control by PLC" signal.
- data transfer via the fieldbus (master/drive) was interrupted.
Remedy:
- check the interconnection of the binector input for "master control by PLC" (p0854).
- check the "master control by PLC" signal and, if required, switch in.
- check the data transfer via the fieldbus (master/drive).
Note:
If the drive should continue to operate after withdrawing "master control by PLC" then fault response must be
parameterized to NONE or the message type should be parameterized as alarm.
A07350 (F)
Drive: Measuring probe parameterized to a digital output
Drive object:
CU_DCP, TM150, TM15DI_DO, TM31
Cause:
The measuring probe is connected to a bi-directional digital input/output and the terminal is set as output.
Alarm value (r2124, interpret decimal):
8: DI/DO 8 (X122.9/X132.1)
9: DI/DO 9 (X122.10/X132.2)
10: DI/DO 10 (X122.12/X132.3)
11: DI/DO 11 (X122.13/X132.4)
12: DI/DO 12 (X132.9)
13: DI/DO 13 (X132.10)
14: DI/DO 14 (X132.12)
15: DI/DO 15 (X132.13)
To the terminal designation:
The first designation is valid for CU320, the second for CU305.
Remedy:
- set the terminal as input (p0728).
- de-select the measuring probe (p0488, p0489, p0580).
F07500
Drive: Power unit data set PDS not configured
Drive object:
TM150, TM15DI_DO, TM31
Cause:
Only for controlled line supply infeed/regenerative feedback units:
The power unit data set was not configured - this means that a data set number was not entered into the drive data
set.
Fault value (r0949, interpret decimal):
Drive data set number of p0185.
Remedy:
The index of the power unit data set associated with the drive data set should be entered into p0185.
F07501
Drive: Motor Data Set MDS not configured
Drive object:
CU_DCP, TM150, TM15DI_DO, TM31
Cause:
Only for power units:
The motor data set was not configured - this means that a data set number was not entered into the associated drive
data set.
Fault value (r0949, interpret decimal):
The fault value includes the drive data set number of p0186.
Remedy:
The index of the motor data set associated with the drive data set should be entered into p0186.
F07502
Drive: Encoder Data Set EDS not configured
Drive object:
CU_DCP, TM150, TM15DI_DO, TM31
Cause:
Only for power units:
The encoder data set was not configured - this means that a data set number was not entered into the associated
drive data set.
Fault value (r0949, interpret decimal):
The fault value includes the drive data set number of p0187, p0188 and p0189.
The fault value is increased by 100 * encoder number (e.g. for p0189: Fault value 3xx with xx = data set number).
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...