2 Parameters
2.2 List of parameters
SINAMICS DCP
254
List Manual (LH21), 05/2016
Description:
Sets the signal source for digital output 2 (DO 2, X177.21) on the CUD.
Note:
DO: Digital Output
Description:
Sets the signal source for digital output 3 (DO 3, X177.22) on the CUD.
Note:
DO: Digital Output
Description:
Sets the delay time for digital output 0 (DO 0, X177.19) on the CUD.
Note:
DO: Digital Output
Description:
Sets the delay time for digital output 1 (DO 1, X177.20) on the CUD.
Note:
DO: Digital Output
Description:
Sets the delay time for digital output 2 (DO 2, X177.21) on the CUD.
Note:
DO: Digital Output
Description:
Sets the delay time for digital output 3 (DO 3, X177.22) on the CUD.
Note:
DO: Digital Output
p50773
BI: CUD digital output 2 signal source / CUD DO 2 s_src
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
Unsigned32 / Binary
Func. diagram:
2055
Min Max
Factory
setting
- -
0
p50774
BI: CUD digital output 3 signal source / CUD DO 3 s_src
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
Unsigned32 / Binary
Func. diagram:
2055
Min Max
Factory
setting
- -
0
p50775
CUD digital output 0 delay time / CUD DO 0 t_del
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
2055
Min Max
Factory
setting
0 [ms]
10000 [ms]
0 [ms]
p50776
CUD digital output 1 delay time / CUD DO 1 t_del
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
2055
Min Max
Factory
setting
0 [ms]
10000 [ms]
0 [ms]
p50777
CUD digital output 2 delay time / CUD DO 2 t_del
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
2055
Min Max
Factory
setting
0 [ms]
10000 [ms]
0 [ms]
p50778
CUD digital output 3 delay time / CUD DO 3 t_del
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
2055
Min Max
Factory
setting
0 [ms]
10000 [ms]
0 [ms]
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...