SINAMICS DCP
List Manual (LH21), 05/2016
111
2 Parameters
2.2 List of parameters
Dependency:
Refer to: p2103, p2104, p2105, p2106, p2107, p2108, p2112, p2116, p2117, p3110, p3111, p3112
Description:
Display and BICO output for status word 1 of faults and alarms.
Note:
Re bit 03, 05, 07:
These bits are set if at least one fault/alarm occurs. Data is entered into the fault/alarm buffer with delay. This is the
reason that the fault/alarm buffer should only be read if, after "fault present" or "alarm present" has occurred, a
change in the buffer was also detected (r0944, r9744, r2121).
Re bit 06, 08:
These status bits are used for internal diagnostic purposes only.
Re bit 12, 11:
These status bits are used for the classification of internal alarm classes and are intended for diagnostic purposes
only on certain automation systems with integrated SINAMICS functionality.
Description:
Display and BICO output for status word 1 of faults and alarms.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
07
Acknowledge fault
Yes
No
8060
10
External alarm 1 (A07850) effective
Yes
No
8065
11
External alarm 2 (A07851) effective
Yes
No
8065
12
External alarm 3 (A07852) effective
Yes
No
8065
13
External fault 1 (F07860) effective
Yes
No
8060
14
External fault 2 (F07861) effective
Yes
No
8060
15
External fault 3 (F07862) effective
Yes
No
8060
r2139.0...15
CO/BO: Status word faults/alarms 1 / ZSW fault/alarm 1
CU_DCP, DCP_CTRL
Can be changed:
-
Access level:
2
Data type:
Unsigned16
Func. diagram:
2548, 8060,
8065
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Being acknowledged
Yes
No
-
01
Acknowledgment required
Yes
No
-
03
Fault present
Yes
No
8060
05
Safety message present
Yes
No
-
06
Internal message 1 present
Yes
No
-
07
Alarm present
Yes
No
8065
08
Internal message 2 present
Yes
No
-
11
Alarm class bit 0
High
Low
-
12
Alarm class bit 1
High
Low
-
13
Maintenance required
Yes
No
-
14
Maintenance urgently required
Yes
No
-
15
Fault gone/can be acknowledged
Yes
No
-
r2139.0...15
CO/BO: Status word faults/alarms 1 / ZSW fault/alarm 1
TM150, TM15DI_DO,
TM31
Can be changed:
-
Access level:
2
Data type:
Unsigned16
Func. diagram:
2548
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Being acknowledged
Yes
No
-
01
Acknowledgment required
Yes
No
-
03
Fault present
Yes
No
8060
05
Safety message present
Yes
No
-
06
Internal message 1 present
Yes
No
-
07
Alarm present
Yes
No
8065
08
Internal message 2 present
Yes
No
-
11
Alarm class bit 0
High
Low
-
12
Alarm class bit 1
High
Low
-
13
Maintenance required
Yes
No
-
14
Maintenance urgently required
Yes
No
-
15
Fault gone/can be acknowledged
Yes
No
-
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...