4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
432
List Manual (LH21), 05/2016
A02011
Function generator: The actual drive speed is not zero
Drive object:
All objects
Cause:
The speed actual value of a drive selected for connection is greater than the value for the standstill detection set
using p1226.
Remedy:
Set the relevant drives to zero speed before starting the function generator.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
A02015
Function generator: Drive enable signals missing
Drive object:
All objects
Cause:
The master control and/or enable signals are missing to connect to the specified drive.
Remedy:
Fetch the master control to the specified drive object and set all enable signals.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
A02016
Function generator: Magnetizing running
Drive object:
All objects
Cause:
Magnetizing has not yet been completed on a drive object specified for connection.
Alarm value (r2124, interpret decimal):
Number of the drive object involved.
Remedy:
Wait for magnetizing of the motor (r0056.4).
Note:
The alarm is reset as follows:
- restart the function generator.
A02020
Function generator: Parameter cannot be changed
Drive object:
All objects
Cause:
This parameter setting cannot be changed when the function generator is active (p4800 = 1).
See also: p4810, p4812, p4813, p4820, p4821, p4822, p4823, p4824, p4825, p4826, p4827, p4828, p4829
Remedy:
- stop the function generator before parameterizing (p4800 = 0).
- if required, start the function generator (p4800 = 1).
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
See also: p4800 (Function generator control)
A02025
Function generator: Period too short
Drive object:
All objects
Cause:
The value for the period is too short.
See also: p4821 (Function generator period)
Remedy:
Check and adapt the value for the period.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
See also: p4821 (Function generator period)
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...