2 Parameters
2.2 List of parameters
SINAMICS DCP
130
List Manual (LH21), 05/2016
Description:
Sets the signal source for terminal DI/DO 1 (X520.3) of Terminal Module 15 (TM15).
Note:
Prerequisite: The DI/DO must be set as an output (p4028.1 = 1).
DI/DO: Bidirectional Digital Input/Output
Description:
Sets the signal source for the digital output DO 1 (X542.4, X542.5, X542.6) of Terminal Module 31 (TM31).
Digital output 1 of TM31 is a relay output.
If the signal at the binector input p4031 is low, then terminal COM 1 (X542.5) is connected to NC 1 (X542.4). This
connection also matches the mechanical quiescent setting of the relay.
If the signal at the binector input p4031 is high, then terminal COM 1 (X542.5) is connected to NO 1 (X542.6).
Note:
DO: Digital Output
NC: Normally Closed contact
NO: Normally Open contact
Description:
Sets the signal source for terminal DI/DO 2 (X520.4) of Terminal Module 15 (TM15).
Note:
Prerequisite: The DI/DO must be set as an output (p4028.2 = 1).
DI/DO: Bidirectional Digital Input/Output
Description:
Sets the signal source for terminal DI/DO 3 (X520.5) of Terminal Module 15 (TM15).
Note:
Prerequisite: The DI/DO must be set as an output (p4028.3 = 1).
DI/DO: Bidirectional Digital Input/Output
Description:
Sets the signal source for terminal DI/DO 4 (X520.6) of Terminal Module 15 (TM15).
Note:
Prerequisite: The DI/DO must be set as an output (p4028.4 = 1).
DI/DO: Bidirectional Digital Input/Output
p4031
BI: TM15DI/DO signal source for terminal DI/DO 1 / TM15D S_src DI/DO1
TM15DI_DO
Can be changed:
U, T
Access level:
1
Data type:
Unsigned32 / Binary
Func. diagram:
9400
Min Max
Factory
setting
- -
0
p4031
BI: TM31 signal source for terminal DO 1 / TM31 s_src DO 1
TM31
Can be changed:
U, T
Access level:
1
Data type:
Unsigned32 / Binary
Func. diagram:
9549, 9556
Min Max
Factory
setting
- -
0
p4032
BI: TM15DI/DO signal source for terminal DI/DO 2 / TM15D S_src DI/DO2
TM15DI_DO
Can be changed:
U, T
Access level:
1
Data type:
Unsigned32 / Binary
Func. diagram:
9400
Min Max
Factory
setting
- -
0
p4033
BI: TM15DI/DO signal source for terminal DI/DO 3 / TM15D S_src DI/DO3
TM15DI_DO
Can be changed:
U, T
Access level:
1
Data type:
Unsigned32 / Binary
Func. diagram:
9400
Min Max
Factory
setting
- -
0
p4034
BI: TM15DI/DO signal source for terminal DI/DO 4 / TM15D S_src DI/DO4
TM15DI_DO
Can be changed:
U, T
Access level:
1
Data type:
Unsigned32 / Binary
Func. diagram:
9400
Min Max
Factory
setting
- -
0
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...