2 Parameters
2.2 List of parameters
SINAMICS DCP
218
List Manual (LH21), 05/2016
Notice:
When the DHCP mode is active (p8944 > 0), then PROFINET communication via this interface is no longer possible!
However, the interface can be used by the STARTER/SCOUT commissioning tool.
Note:
The active DHCP mode is displayed in parameter r8954.
The interface configuration (p8940 and following) is activated with p8945.
The parameter is not influenced by setting the factory setting.
If value = 0:
DHCP deactivated.
If value = 1:
Reserved.
If value = 2:
DHCP activated. The MAC address of this interface is used for client identification.
If value = 3:
DHCP activated. The station name of this interface is used for client identification.
Description:
Sets the activation of the interface configuration for the Communication Board Ethernet 20/25 (CBE20/CBE25).
p8945 is automatically set to 0 at the end of an operation.
Value:
0:
No function
2:
Save and activate configuration
3:
Delete configuration
Dependency:
Refer to: p8940, p8941, p8942, p8943, p8944
Notice:
When the DHCP mode is active (p8944 > 0), then PROFINET communication via this interface is no longer possible!
However, the interface can be used by the STARTER/SCOUT commissioning tool.
Note:
For CBE20, the parameter is only valid for firmware version "PROFINET Device" (p8835 = 1) or "Ethernet/IP" (p8835
= 4). Otherwise, it is locked.
This restriction is not applicable for the CBE25.
Re p8945 = 2:
The interface configuration (p8940 and following) is saved and activated after the next POWER ON.
Re p8945 = 3:
The factory setting of the interface configuration is loaded after the next POWER ON.
Description:
Displays the active station name for the Communication Board Ethernet 20/25 (CBE20/CBE25).
Description:
Displays the active IP address for the Communication Board Ethernet 20/25 (CBE20/CBE25).
p8945
CBE2x interface configuration / CBE2x int config
CU_DCP (PROFINET
CBE20)
Can be changed:
U, T
Access level:
3
Data type:
Integer16
Func. diagram:
-
Min Max
Factory
setting
0 3
0
r8950[0...239]
CBE2x Name of Station active / CBE2x Name act
CU_DCP (PROFINET
CBE20)
Can be changed:
-
Access level:
3
Data type:
Unsigned8
Func. diagram:
-
Min Max
Factory
setting
- -
-
r8951[0...3]
CBE2x IP Address of Station active / CBE2x IP act
CU_DCP (PROFINET
CBE20)
Can be changed:
-
Access level:
3
Data type:
Unsigned8
Func. diagram:
-
Min Max
Factory
setting
0 255
-
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...