SINAMICS DCP
List Manual (LH21), 05/2016
271
2 Parameters
2.2 List of parameters
Description:
Sets the signal source for the current setpoint for manual operation.
Manual operation is selected via binector input p54001 = 0 signal.
Dependency:
Refer to: p54001
Note:
MPP: maximum power point (point along the characteristic with the maximum power)
Description:
Sets the signal source for switching over between manual and automatic operation.
BI: p54001 = 1 signal:
Automatic operation is selected.
BI: p54001 = 0 signal:
Manual operation is selected.
Dependency:
Refer to: p54000
Note:
MPP: maximum power point (point along the characteristic with the maximum power)
Description:
Sets the signal source for the current limit of the MPP tracker.
Note:
MPP: maximum power point (point along the characteristic with the maximum power)
Description:
Sets the signal source for the start value of the MPP tracker current.
Note:
MPP: maximum power point (point along the characteristic with the maximum power)
Description:
Sets the search interval for the MPP tracker.
In this time interval, the MPP tracker changes the current setpoint in order to identify the point with the maximum
power.
Note:
MPP: maximum power point (point along the characteristic with the maximum power)
p54000
CI: MPP tracker current setpoint manual signal source / MPPT I_s man s_src
DCP_CTRL
Can be changed:
T
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Func. diagram:
6700
Min Max
Factory
setting
- -
2050[1]
p54001
BI: MPP tracker manual/automatic signal source / MPPT man/aut s_src
DCP_CTRL
Can be changed:
T
Access level:
2
Data type:
Unsigned32 / Binary
Func. diagram:
6700
Min Max
Factory
setting
- -
1
p54002
CI: MPP tracker current limit signal source / MPPT I_limit s_src
DCP_CTRL
Can be changed:
T
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Func. diagram:
6700
Min Max
Factory
setting
- -
1
p54003
CI: MPP tracker current start value signal source / MPPT I stVal s_src
DCP_CTRL
Can be changed:
T
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Func. diagram:
6700
Min Max
Factory
setting
- -
55112[0]
p54005
MPP tracker search interval / MPPT srch interv
DCP_CTRL
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
6700
Min Max
Factory
setting
0.10 [s]
100.00 [s]
2.00 [s]
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...