2 Parameters
2.2 List of parameters
SINAMICS DCP
136
List Manual (LH21), 05/2016
Displays the actual input current in mA when set as current input and with the load resistor switched in.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
The type of analog input AI x (voltage or current input) is set using p4056.
Refer to: p4056
Note:
AI: Analog Input
Description:
Sets the smoothing time constant of the 1st-order low pass filter for the analog inputs of Terminal Module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Note:
AI: Analog Input
Description:
Displays the currently referred input value of the analog inputs of Terminal Module 31 (TM31).
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Note:
AI: Analog Input
Description:
Sets the type of analog inputs of Terminal Module 31 (TM31).
p4056[x] = 0, 4 correspond to a voltage input (r4052, p4057, p4059 are displayed in V).
p4056[x] = 2, 3, 5 correspond to a current input (r4052, p4057, p4059 are displayed in mA).
In addition, the associated switch S5 must be appropriately set.
AI 0: S5.0 = V --> voltage input, S5.0 = I --> current input (burden resistor = 250 Ohm)
AI 1: S5.1 = V --> voltage input, S5.1 = I --> current input (burden resistor = 250 Ohm)
Value:
0:
Unipolar voltage input (0 V ... +10 V)
2:
Unipolar current input (0 mA ... +20 mA)
3:
Unipolar current input monitored (+4 mA to +20 mA)
4:
Bipolar voltage input (-10 V ... +10 V)
5:
Bipolar current input (-20 mA to +20 mA)
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Warning:
The maximum voltage difference between the analog input terminals AI+, AI- and the ground of the TM31 (X520.6,
X530.3) may not exceed 35 V.
For operation with the load resistor switched in, the voltage between the differential inputs AI+ and AI- may not
exceed 15 V or the impressed current of 60 mA; if this is not carefully observed, the input will be damaged.
Notice:
For operation as a voltage input/current input, switch S5.0 or S5.1 must be appropriately set.
p4053[0...1]
TM31 analog inputs smoothing time constant / TM31 AI T_smooth
TM31
Can be changed:
U, T
Access level:
1
Data type:
FloatingPoint32
Func. diagram:
9566, 9568
Min Max
Factory
setting
0.0 [ms]
1000.0 [ms]
0.0 [ms]
r4055[0...1]
CO: TM31 analog inputs actual value in percent / TM31 AI value in %
TM31
Can be changed:
-
Access level:
1
Data type:
FloatingPoint32
Func. diagram:
9549, 9566,
9568
Min Max
Factory
setting
- [%]
- [%]
- [%]
p4056[0...1]
TM31 analog inputs type / TM31 AI type
TM31
Can be changed:
U, T
Access level:
1
Data type:
Integer16
Func. diagram:
9566, 9568
Min Max
Factory
setting
0 5
4
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...