SINAMICS DCP
List Manual (LH21), 05/2016
157
2 Parameters
2.2 List of parameters
Recommendation:
The following connector inputs can use these connector outputs for interconnection:
- CI: p0603
- CI: p0608[0...3]
- CI: p0609[0...3]
- CI: p2051
Index:
[0] = Group 0
[1] = Group 1
[2] = Group 2
Dependency:
Refer to: r4105, p4111, r4112, r4113
Note:
If one group is assigned sensor type "PTC" or "bimetal NC contact", then the average value -300 °C is output.
Description:
Sets the effect for an error of a sensor of a group for Terminal Module TM150 (TM150).
For p4117 = 0, the following applies:
The defective temperature sensor assigned to a group is not take into account when forming the group.
For p4117 = 1, the following applies:
For a sensor error, for the maximum value, minimum value and average value of the corresponding group, a value of
-300 °C is output.
Value:
0:
Skip sensor
1:
Output value = -300 °C
Index:
[0] = Group 0
[1] = Group 1
[2] = Group 2
Dependency:
Refer to: r4105, p4111, r4112, r4113, r4114
Description:
Sets the hysteresis for the fault threshold/alarm threshold (p4102[0...23]) for the Terminal Module 150 (TM150).
Index:
[0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
[6] = Temperature channel 6
[7] = Temperature channel 7
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Dependency:
Refer to: p4102, p4103, r4104, r4105
Note:
The following applies for a corresponding alarm:
- Remains until the temperature actual value (r4105[x]) reaches or falls below the threshold value (p4102[2x] -
hysteresis (p4118[x]).
The following applies for a corresponding fault:
- Remains until the temperature actual value (r4105[x]) reaches or falls below the threshold value (p4102[2x+1]) -
hysteresis (p4118[x]) and the fault has been acknowledged.
p4117[0...2]
TM150 group sensor error effect / TM150 error effect
TM150
Can be changed:
U, T
Access level:
1
Data type:
Integer16
Func. diagram:
9625
Min Max
Factory
setting
0 1
0
p4118[0...11]
TM150 fault threshold/alarm threshold hysteresis / TM150 thresh hyst
TM150
Can be changed:
T
Access level:
1
Data type:
Unsigned16
Func. diagram:
9626, 9627
Min Max
Factory
setting
0 [K]
50 [K]
5 [K]
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...