SINAMICS DCP
List Manual (LH21), 05/2016
153
2 Parameters
2.2 List of parameters
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Dependency:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[0...11] = 1, 4), the following applies:
- below the nominal response temperature, r4105[0...11] = -50 °C.
- above the nominal response temperature, r4105[0...11] = 250 °C.
For sensor type "KTY84", "PT100", "PT1000" (p4100[0...11] = 2, 5, 6) the following applies:
- the displayed value corresponds to the temperature actual value.
Refer to: p4100, p4111, r4112, r4113, r4114
Note:
r4105[0...11] = -300 °C is displayed in the following cases:
- temperature actual value invalid (F35920 ... F35931 output).
- no sensor selected (p4100[0...11] = 0).
The temperature actual values can be grouped using p4111[0...2] and the maximum value, minimum value as well as
the average value for each group evaluated (r4112[0...2], r4113[0...2], r4114[0...2]).
Description:
Displays the temperature actual value for the Terminal Module 31 (TM31)
Dependency:
For sensor type "PTC thermistor" (p4100 = 1), the following applies:
- below the nominal response temperature, r4105 = -50°C.
- above the nominal response temperature, r4105 = 250 °C.
For sensor type "KTY84" (p4100 = 2), the following applies:
- the displayed value corresponds to the temperature actual value.
Refer to: p4100
Note:
r4105 = -300 °C is displayed in the following cases:
- temperature actual value invalid (F35920 output).
- no sensor selected (p4100 = 0).
The temperature sensor is connected at terminals X522.7(+) and X522.8(-).
Description:
Sets the measuring method for the terminal block X531 ... X536 for the Terminal Module 150 (TM150).
Re p4108[0...5] = 0 (1x2 wire evaluation):
- the temperature sensor is connected at terminals 1(+) and 2(-).
Re p4108[0...5] = 1 (2x2 wire evaluation):
- The first temperature sensor is connected at terminals 1(+) and 2(-).
- The second temperature sensor is connected at terminals 3(+) and 4(-).
Re p4108[0...5] = 2 (3 wire evaluation):
- the temperature sensor is connected at terminals 3(+) and 4(-).
- the measuring conductor is connected at terminal 1(+).
- terminals 2(-) and 4(-) must be jumpered.
Re p4108[0...5] = 3 (4 wire evaluation):
- the temperature sensor is connected at terminals 3(+) and 4(-).
- the measuring conductor is connected at terminals 1(+) and 2(-).
Value:
0:
1x2 wire evaluation
1:
2x2 wire evaluation
2:
3 wire evaluation
3:
4 wire evaluation
r4105
CO: TM31 temperature actual value / TM31 temp_act val
TM31
Can be changed:
-
Access level:
1
Data type:
FloatingPoint32
Func. diagram:
9549, 9576
Min Max
Factory
setting
- [°C]
- [°C]
- [°C]
p4108[0...5]
TM150 terminal block measuring method / TM150 meas method
TM150
Can be changed:
T
Access level:
1
Data type:
Integer16
Func. diagram:
9625, 9626,
9627
Min Max
Factory
setting
0 3
1
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...