SINAMICS DCP
List Manual (LH21), 05/2016
117
2 Parameters
2.2 List of parameters
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p2108, p3110, p3111
Refer to: F07862
Description:
Sets the signal source for the negated enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p2108, p3110, p3111
Refer to: F07862
Description:
Display and BICO output for the status of the NAMUR message bit bar.
The faults and alarms are assigned to the appropriate signaling/message classes and influence a specific message
bit.
Note:
Re bit 00:
Hardware or software malfunction was identified. Carry out a POWER ON of the component involved. If it occurs
again, contact the hotline.
Re bit 01:
A line supply fault has occurred (phase failure, voltage level, ...). Check the line supply / fuses. Check the supply
voltage. Check the wiring.
Re bit 02:
The DC link voltage has assumed an inadmissibly high value. Check the dimensioning of the system (line supply,
reactor, voltages). Check the infeed settings.
Re bit 03:
An inadmissible operating state of the power electronics was identified (overcurrent, overtemperature, IGBT failure,
...). Check that the permissible load cycles are maintained. Check the ambient temperatures (fan).
p3112[0...n]
BI: External fault 3 enable negated / Ext flt 3 enab neg
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
Unsigned32 / Binary
Func. diagram:
-
Min Max
Factory
setting
- -
0
r3113.0...15
CO/BO: NAMUR message bit bar / NAMUR bit bar
CU_DCP, TM150,
TM15DI_DO, TM31
Can be changed:
-
Access level:
3
Data type:
Unsigned16
Func. diagram:
-
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Fault converter information
electronics/software error
Yes
No
-
01
Network fault
Yes
No
-
02
DC link overvoltage
Yes
No
-
03
Fault drive converter power electronics
Yes
No
-
04
Drive converter overtemperature
Yes
No
-
05
Ground fault
Yes
No
-
06
Motor overload
Yes
No
-
07
Bus error
Yes
No
-
08
External safety-relevant shutdown
Yes
No
-
09
Mot encoder fault
Yes
No
-
10
Error communication internal
Yes
No
-
11
Fault infeed
Yes
No
-
15
Other faults
Yes
No
-
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...