2 Parameters
2.2 List of parameters
SINAMICS DCP
284
List Manual (LH21), 05/2016
Description:
Display and BICO output for the status of the current setpoint.
Description:
Sets the load profile.
If value = 0:
Short time current = base load current = rated device current
If value = 1:
Short time current = base load current = p55081 * rated device current
In this operating mode, at low ambient temperatures, an increased current is continuously permitted. However, the
temperature-dependent derating already starts at a lower ambient temperature than for operation without increased
current.
If value = 2:
Short time current = 150 % * base load current
If value = 3:
Short time current = 160 % * base load current
Value:
0:
No overload
1:
Increased current
2:
Low overload
3:
High overload
Description:
Sets the permissible current increase for the load profile "increased current" (p55080 = 1).
Description:
Display and connector output for various calculated temperatures.
Index:
[0] = Barrier layer temperature at IGBT T1A
[1] = Barrier layer temperature at IGBT T1B
[2] = Barrier layer temperature at IGBT T2A
[3] = Barrier layer temperature at IGBT T2B
[4] = Barrier layer temperature at free-wheeling diode D1A
[5] = Barrier layer temperature at free-wheeling diode D1B
[6] = Barrier layer temperature at free-wheeling diode D2A
[7] = Barrier layer temperature at free-wheeling diode D2B
[8] = Maximum permissible barrier layer temperature
r55075.0...2
CO/BO: Current setpoint status / I_set status
DCP_CTRL
Can be changed:
-
Access level:
2
Data type:
Unsigned16
Func. diagram:
6805
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Setpoint very low
Yes
No
6805
01
Setpoint positive
Yes
No
6805
02
Setpoint negative
Yes
No
6805
p55080
Dynamic overload load profile / Dyn overload prof
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
Integer16
Func. diagram:
6808
Min Max
Factory
setting
0 3
0
p55081
Dynamic overload current increase / Dyn overld I_incr
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
6808
Min Max
Factory
setting
0.00 [%]
20.00 [%]
0.00 [%]
r55082[0...8]
CO: Dynamic overload temperatures calculated / Dyn overld T_calc
DCP_CTRL
Can be changed:
-
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
6808
Min Max
Factory
setting
- [°C]
- [°C]
- [°C]
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...