SINAMICS DCP
List Manual (LH21), 05/2016
139
2 Parameters
2.2 List of parameters
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description:
Sets the signal source to invert the analog inputs signals of Terminal Module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description:
Sets the noise suppression window of the analog inputs for Terminal Module 31 (TM31).
Changes less than the window are suppressed.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Note:
AI: Analog Input
Description:
Sets the signal source for the enable signal of the analog inputs of Terminal Module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description:
Sets the signal source for the analog outputs of Terminal Module 31 (TM31).
Index:
[0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Note:
AO: Analog Output
Description:
Displays the actual referred output value of the analog outputs of Terminal Module 31 (TM31).
Index:
[0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
p4067[0...1]
BI: TM31 analog inputs invert signal source / TM31 AI inv s_src
TM31
Can be changed:
U, T
Access level:
3
Data type:
Unsigned32 / Binary
Func. diagram:
9566, 9568
Min Max
Factory
setting
- -
0
p4068[0...1]
TM31 analog inputs window to suppress noise / TM31 AI window
TM31
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
9566, 9568
Min Max
Factory
setting
0.00 [%]
20.00 [%]
0.00 [%]
p4069[0...1]
BI: TM31 analog inputs signal source for enable / TM31 AI enable
TM31
Can be changed:
U, T
Access level:
3
Data type:
Unsigned32 / Binary
Func. diagram:
9566, 9568
Min Max
Factory
setting
- -
1
p4071[0...1]
CI: TM31 analog outputs signal source / TM31 AO s_src
TM31
Can be changed:
U, T
Access level:
1
Data type:
Unsigned32 / FloatingPoint32
Func. diagram:
9549, 9572
Min Max
Factory
setting
- -
0
r4072[0...1]
TM31 analog outputs output value currently referred / TM31 AO outp_val
TM31
Can be changed:
-
Access level:
1
Data type:
FloatingPoint32
Func. diagram:
9572
Min Max
Factory
setting
- [%]
- [%]
- [%]
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...