2 Parameters
2.2 List of parameters
4:
Data set base configuration
29:
Device download
30:
Parameter reset
50:
OA application configuration
55:
OA application installation
Notice:
For p0009 = 10000 the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
The drives can only be powered up outside the device commissioning (the drive enabled). In this case, p0009 must
be 0 (Ready) and the individual drive objects must have already gone into operation (p0010).
p0009 = 1: Device configuration
At the first commissioning of the device, after booting, the device is in the "device configuration" state. To start the
internal automatic first commissioning of the drive unit, p0009 should be set to 0 (Ready) after the ID for the actual
topology (r0098) was transferred into the ID for the target topology (p0099). To do this, it is sufficient to set a single
index value of p0099[x] the same as r0098[x]. Before the device has been completely commissioned, no other
parameter can be changed. After the first commissioning was carried out, in this state, when required, other basic
device configuration parameters can be adapted (e.g. the basic sampling time in p0110).
p0009 = 2: Defines the drive type / function module
In this state, the drive object types and/or the function modules can be changed or selected for the individual drive
objects. To do this, the drive object type can be set using p0107[0...15] and the function can be set using
p0108[0...15] (refer to p0101[0...15]).
p0009 = 3: Drive basic configuration
In this state, after the device has been commissioned for the first time, basic changes can be made for the individual
drive objects (e.g. sampling times in p0111, p0112, p0115 and the number of data sets in p0120, p0130, p0140,
p0170, p0180).
p0009 = 4: Data set basic configuration
In this state, after the device has been commissioned for the first time, for the individual drive objects changes can be
made regarding the assignment of the components (p0121, p0131, p0141, p0151, p0161) to the individual data sets
and the assignment of the power unit, motor and encoder to the drive data sets (p0185, ...).
p0009 = 29: Device download
If a download is made using the commissioning software, the device is automatically brought into this state. After the
download has been completed, p0009 is automatically set to 0 (ready). It is not possible to manually set p0009 to this
value.
p0009 = 30: Parameter reset
In order to bring the complete unit into the "first commissioning" state or to load the parameters saved using p0977, to
start, p0009 must be set to this value. p0976 can then be changed to the required value.
p0009 = 50: OA application configuration
In this state, after the device has been commissioned for the first time, changes can be made for the individual drive
objects regarding the activity (p4956) of the OA applications.
p0009 = 55: OA application installation
OA applications can be installed and/or uninstalled in this state.
Description:
Sets the parameter filter to commission a drive.
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
Value:
0:
Ready
1:
Quick commissioning
4:
Encoder commissioning
15:
Data sets
29:
Only Siemens int
30:
Reserved
Note:
The drive can only be powered up outside the drive commissioning (drive enable). To realize this, this parameter
must be set to 0.
By setting p3900 to a value other than 0, the quick commissioning is completed, and this parameter is automatically
reset to 0.
p0010
Drive commissioning parameter filter / Drv comm. par_filt
DCP_CTRL
Can be changed:
C2(1), T
Access level:
1
Data type:
Integer16
Func. diagram:
-
Min Max
Factory
setting
0 30
1
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...