92
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
Table 3.12 Control Circuit Wire Gauges and Tightening Torques
Terminal
Bare Wire
Crimp Ferrule
Recommended Gauge
mm
2
(AWG)
Applicable Gauge
mm
2
(AWG)
Recommended Gauge
mm
2
(AWG)
Applicable Gauge
mm
2
(AWG)
DI1 - DI8, D0V, DIC, D24V
H1, H2, HC
PI, +10V, -10V, AI1, AI2, AI3, A0V
PO, AO1, AO2, A0V
RS485+, RS485-, A0V
1NO, 1NC, 1CM, 2NO, 2CM, 3NO, 3CM, 4CO,
4CM
E24V, GND
0.75
(18)
•
Stranded wire
0.2 - 1.0
(24 - 18)
•
Solid wire
0.2 - 1.5
(24 - 16)
0.5
(20)
0.25 - 0.5
(24 - 20)
■
Crimp Ferrules
Attach an insulated sleeve when you use crimp ferrules.
Use the CRIMPFOX 6, a crimping tool made by PHOENIX CONTACT.
Figure 3.35 External Dimensions of Crimp Ferrules
Table 3.13 Crimp Ferrule Models and Sizes
Wire Gauge
mm
2
(AWG)
Model
L (mm)
L1 (mm)
φ
d1 (mm)
φ
d2 (mm)
0.25 (24)
AI 0.25-8YE
12.5
8
0.8
2.0
0.34 (22)
AI 0.34-8TQ
12.5
8
0.8
2.0
0.5 (20)
AI 0.5-8WH,
AI 0.5-8OG
14
8
1.1
2.5
◆
Wiring the Control Circuit Terminal
WARNING!
Electrical Shock Hazard. Do not remove covers or touch circuit boards while the drive is energized. Failure to obey
can cause death or serious injury.
NOTICE:
Isolate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2, W/T3, -, +1, +2)
and other high-power wiring. Incorrect wiring procedures could cause drive malfunction because of electrical interference.
NOTICE:
Isolate contact output terminals 1NO, 1NC, 1CM, 2NO, 2CM, 3NO, 3CM, 4CO, 4CM from other control circuit wiring.
The drive and connected equipment will malfunction or the drive can trip because of incorrect wiring.
NOTICE:
Use a class 2 power supply when connecting to the control terminals. Refer to NEC Article 725 Class 1, Class 2, and
Class 3 Remote-Control, Signaling, and Power Limited Circuits for requirements concerning class 2 power supplies. Improper
application of peripheral devices could result in drive performance degradation due to improper power supply.
NOTICE:
Insulate wire shields with tape or shrink tubing to prevent contact with other signal lines or equipment. Incorrect wiring
procedures could cause the drive or connected equipment to malfunction because of short circuits.
NOTICE:
Connect the shield of shielded cable to the applicable ground terminal. Incorrect equipment grounding could cause
the drive or connected equipment to malfunction or to trip again and again.
Correctly ground the drive terminals and complete main circuit wiring before you wire the control circuit.
Remove the keypad and front cover.
1.
Push in on the tabs on the both sides of the USB port board to release the board from the bracket. Pull the
board forward to remove it.
NOTICE:
Make sure that the USB port board is safe after you remove it from the bracket. Failure to obey will cause
damage to the USB port board.
Note:
You can temporarily store the USB port board with the temporary placement holes on the drive. The location of the temporary
placement holes changes by drive model.
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...