SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
779
■
L3-21 OVSup Acc/Dec Gain
No.
(Hex.)
Name
Description
Default
(Range)
L3-21
(0466)
Expert
OVSup Acc/Dec Gain
Sets the proportional gain to calculate acceleration and deceleration rates.
Determined by A1-02
(0.10 - 10.00)
Set one of these parameters to enable L3-21:
•
L2-29 = 2 [KEB Method = Single KEB2 Ride-Thru]
•
L3-04 = 1 [StallP@Decel Enable = Enabled]
and
L3-50 = 1 [StallP@Decel Mode = Automatic Decel
Reduction]
•
L3-11 = 1 [Overvolt Supression Select = Enabled]
•
H1-xx = 42 or 43 [DI Function Select = KEB Thru2 NC or KEB Thru2 NO]
Note:
•
If stall prevention during deceleration function causes large speed or current ripples and
L2-29 = 1, H1-xx = 42 or 43
, or
L3-04 = 2
,
gradually decrease this parameter in 0.05-unit increments. If the drive detects
ov [Overvoltage]
or
oC [Overcurrent]
, decrease this
parameter. If you decrease the gain too much, it can cause a delay in control in the DC bus voltage or the deceleration time could be
longer than the best deceleration time.
•
If sudden increases in the regenerative load cause
ov
faults and
L3-11 = 1
, gradually increase this parameter in 0.1-unit increments. If
there are large speed ripples, gradually decrease this parameter in 0.05-unit increments.
■
L3-22 StallP@Acc Deceleration Time
No.
(Hex.)
Name
Description
Default
(Range)
L3-22
(04F9)
StallP@Acc Deceleration
Time
Sets the momentary deceleration time that the drive will use when it tries to accelerate a PM
motor and detected motor stalls. This function is applicable when
L3-01 = 2 [StallP Mode@Accel
= General Purpose]
.
0.0 s
(0.0 - 6000.0 s)
Set this parameter to 0.0 s to disable this function. The drive will decelerates in the deceleration time applicable at
the time when a motor stall occurs.
■
L3-23 CHP Stall P Selection
No.
(Hex.)
Name
Description
Default
(Range)
L3-23
(04FD)
CHP Stall P Selection
Sets the function to automatically decrease the Stall Prevention Level during Run for constant
output ranges.
1
(1, 2)
1 : Level@L3-06
The drive uses the level set in
L3-06 [StallP Level@Run]
through the full speed range.
2 : Automatic Reduction
The drive decreases the Stall Prevention level during run in the constant power range. The lower limit is 40% of
the
L3-06
value.
■
L3-24 Acc@Rated Torque
No.
(Hex.)
Name
Description
Default
(Range)
L3-24
(046E)
Expert
Acc@Rated Torque
Sets the motor acceleration time to reach the maximum frequency at the motor rated torque for
stopped single-drive motors.
Determined by o2-04, C6-
01, E2-11, and E5-01
(0.001 - 10.000 s)
Set one of these parameters to enable
L3-24
:
•
L2-29 = 2 [KEB Method = Single KEB2 Ride-Thru]
•
L3-04 = 1 [StallP@Decel Enable = Enabled]
and
L3-50 = 1 [StallP@Decel Mode = Automatic Decel
Reduction]
•
L3-11 = 1 [Overvolt Supression Select = Enabled]
•
H1-xx = 42 or 43 [DI Function Select = KEB Thru2 NC or KEB Thru2 NO]
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...